Ard or zd dampers, Transformer – Honeywell ENVIRAZONE PANEL W8835 User Manual

Page 7

Advertising
background image

W8835 ENVIRAZONE PANEL

7

68-0258—04

ARD or ZD Dampers

Wire the ARD or ZD Damper to the panel as shown in Fig. 8.

Multiple dampers can be wired in parallel. Up to five ARD or

ZD dampers can be connected in parallel to one zone. If five to

ten dampers are connected to the panel an additional 40VA

transformer must be connected to the panel.

Fig. 8. Wiring ARD or ZD damper to panel.

RRD

Wire the RRD dampers to the panel as shown in Fig. 9. Two or

more RRD can be wired in tandem as shown in Fig 10. Up to

12 RRD can be wired to one zone. Power the panel with one

40VA transformer if up to 12 dampers are connected to the

panel. Power the panel with two 40VA transformers if up to 26

RRD are connected to the panel.

Fig. 9. Wiring RRD damper to panel.

Fig. 10. Wiring two RRD dampers in parallel.

MARD Dampers or Dampers using ML6161
Motor Actuator

Wire the MARD Damper or other damper using the ML6161

Actuator to the panel as shown in Fig. 11. These floating

control actuators are controlled as two-position devices on the

W8835 panel.

The ML6161 motor causes the damper LED to illuminate green

constantly. To restore damper position indication, mount end

switch 201052B onto the ML6161.

Fig. 11. Wiring MARD Damper or ML6161 Actuator to

panel.

Transformer

Wire the transformers to the panel (see Fig. 12). One 40 VA, 24

Vac transformer is required to operate the panel and up to five

ARD or ZD dampers. The transformer is connected to

terminals R and C. The auxiliary transformer is required if up to

ten dampers are connected to the panel. It is wired to terminals

T1 and T2. If more than five ARD or ZD dampers are required

for one zone of if more than ten ARD or ZD dampers are

required for the W8835, use the Slave Damper Control Relay

(SDCR). Locate the XFRM jumper shown in Fig. 12. These

jumpers are shipped in the open, disconnected position. This is

the correct position when two transformers are used. When

using one transformer to power the panel, place the jumpers in

the closed position. Do this by removing the jumpers and

installing them so they cover both of their respective pins. If

preferred, one 75 VA transformer may be used on this panel

instead of two 40 VA. If this is done, leave the jumpers in the

open, disconnected position and install a jumper between R

and T1. Wire the transformer to R and C.

M6 M4 M1

ZONE

1, 2, 3, ETC.

M1

M6
M4

M31133

M6 M4 M1

ZONE

1, 2, 3

M 1

M 6
M 4

M1
M6
M4

M31134

M1 M4

M20136A

ZONE PANEL

CONNECTIONS

M6

CW

COM

CCW

MARD