Single and multi-stage conventional heat operation, Com led operation, Purge mode – Honeywell ENVIRAZONE PANEL W8835 User Manual

Page 9: Individual zone fan control

Advertising
background image

W8835 ENVIRAZONE PANEL

9

68-0258—04

COM LED Operation

The green COM LED flickers as the W8835 communicates

with the other EnviraCom devices:

LED blinks rapidly—indicates device is currently

transmitting information on the communications bus.

LED blinks once—indicates device received and

acknowledged a message.

LED on constantly— indicates panel failure. Replace panel.

LED off constantly—indicates a wiring problem.

Table 3. LED Indicators

b

b

An LED change precedes the corresponding relay change by as much as six seconds.

Purge Mode

At the end of every call for heat or cool, the panel enters a

Purge mode. DIP 4 configures the panel to purge for two

(default) or three and one-half minutes. DIP switch 5

configures the panel or the HVAC equipment to operate the fan

during purge.

The Purge LED lights to signal that the system is in the Purge

mode. Pressing the purge override button overrides the Purge

mode.

Unless there is a new call for heat or cool during the Purge

mode, all dampers are moved to the Open position at the end

of purge. DIP switch 6 is used if it desired to open all dampers

during the Purge mode.

Table 4. Purge Configuration

Table 5. Fan Control Configuration

Table 6. Purge Damper Configuration

Individual Zone Fan Control

When all zones are satisfied, the fan switch of each thermostat

controls the fan operation for that zone. When the fan setting is

“ On”, the fan is energized, the fan LED illuminates and the

dampers close to zones where the fan setting is “Auto”. If there

is a call for heat or cool during this time, the fan mode ceases,

and the heat or cool call is honored. When the zone calling is

satisfied, and Purge mode has ended, the fan call resumes.

Single and Multi-Stage Conventional
Heat Operation

The panel can control up to three stages of heating and two

stages of cooling based on thermostat demand. Set DIP

switches 1 and 2 for 1, 2 or 3 stages of heat. Set DIP switch 7

for one or two stages of cooling.

Table 7. Conventional Equipment Configuration

LED

Color

Illuminated

Not Illuminated

Heat

Red

Heat call.

No heat calls.

Cool

Green

Cool call.

No cool calls.

Purge

Amber

Purge mode.

Not in Purge mode.

Fan

Green

Fan only call.

No fan only call.

Em Heat

Red

Emergency Heat mode.

Not in Emergency Heat mode.

Zone 1, 2, 3

Green

Damper is open or opening.

Damper is closed or closing.

DIP Switch

Number

Status

Purge

4

Off (Down)

3.5 minutes purge

4

On (Up)

2 minutes purge

DIP Switch

Number

Status

Fan Control

5

Off (Down)

Panel control of fan

in Purge

5

On (Up)

HVAC control of fan

in Purge

DIP Switch

Number

Status

Purge Damper

6

On (Up)

Last zone(s) calling

open during Purge

6

Off (Down)

Open all dampers

during Purge

1 Stage Cooling

Equipment Type

DIP 1

DIP 2

1 Stage Conventional

On (Up)

On (Up)

2 Stage Conventional

On (Up)

Off (Down)

3 Stage Conventional

Off (Down)

On (Up)

2 Stage Cooling

Cooling Stage

DIP7

1 Stage

On (Up)

2 Stage

Off (Down)