Chase installation, Chimney height, Chimney height for vertical termination – Heatiator Heatilator BCDV36 User Manual

Page 12: Chimney installation, Firestop spacer, Multiple vertical termination, Termination installation, Firestop spacer/chimney installation, Builder's choice series installation instructions

Advertising
background image

33606 Rev D

12

01-03

BUILDER'S CHOICE SERIES INSTALLATION INSTRUCTIONS

c. Firestop Spacer/Chimney Installation

Frame an opening and install an FS6 Firestop

Spacer whenever the vent penetrates a ceiling/

floor area, as shown in Figure 16. Frame the

opening with the same sized lumber as used in

the ceiling/floor joists. Do not pack insulation

around the chimney.

d. Chase/Termination Installation

Figures 17 and 18, and Table 1 specify minimum

chimney heights for various pitched roofs.
These chimney heights are necessary for safety

and do not ensure draft-free operation. Trees,

buildings, adjoining roof lines, adverse conditions,

etc. may create a need for a taller chimney should

down drafting occur.

Figure 16

Installing the Firestop Spacer

Figure 17

Chimney Height for Vertical Termination

Roof Pitch

H (Min.) Ft.

Flat to 6/12

1.0

6/12 to 7/12

1.25

Over 7/12 to 8/12

1.5

Over 8/12 to 9/12

2.0

Over 9/12 to 10/12

2.5

Over 10/12 to 11/12

3.25

Over 11/12 to 12/12

4.0

Over 12/12 to 14/12

5.0

Over 14/12 to 16/12

6.0

Over 16/12 to 18/12

7.0

Over 18/12 to 20/12

7.5

Over 20/12 to 21/12

8.0

Table 1

Chimney Height

Note:

To ensure proper operation, verify all venting and

the termination are unobstructed.

Figure 18

Multiple Vertical Termination Clearances