DEAN MILLIVOLT GAS FRYERS (CE)

CHAPTER 4: FRYER OPERATION

4-3

4.1.1 Pilot Lighting Procedures (cont.)

9. If the pilot does not stay lit, depress the white pilot light button and re-light the pilot, holding the

button in longer before releasing. Trapped air may necessitate re-lighting the pilot several times
until a constant gas flow is attained.


10. When the pilot stays lit, release the white pilot light button.

11. Turn the thermostat to any "ON" setting and ensure the main burner ignites from the pilot.



4.2 Boil-Out Procedure

DANGER

Never leave the fryer unattended during the boil-out process. If the boil-out solution

boils over, turn the fryer off immediately and let the solution cool for a few minutes

before resuming the process.

WARNING

Do not drain boil-out solution into a shortening disposal unit, a built-in filtration unit,

or a portable filter unit. These units are not intended for this purpose, and will be

damaged by the solution.

DANGER

Remove all drops of water from the frypot before filling with cooking oil or

shortening. Failure to do so will cause spattering of hot liquid when the oil or

shortening is heated to cooking temperature and may cause injury to nearby

personnel.


1. Empty frypot and pour in cleaning solution concentrate. Add water to the bottom OIL LEVEL

line scribed in the back of the frypot.

2. Set the operating thermostat-dial/temperature controller to 107°C (225°F), just above that of

boiling water.

3. The main burner will ignite.

4. Reset the temperature controller to 93°C (200°F).

5. The burners should shut off, just as the boil-out solution reaches setpoint.

CAUTION

If the pilot and main burner go out, the fryer(s) MUST be left completely shut down at

least 5 minutes before lighting.