VENTING INSTALLATION

Continued

Pitch

Slope Opening

"A" Max.

Used Flashing

Model No.

Flat

15"

V6F-8DM

0-6/12

26.6°

16

1

/

8

"

V6F-8DM

6/12- 12/12 45.0°

20

3

/

8

"

V12F-8DM

4. Remove shingles around opening mea-

sured. Cut out this section.

5. Add next sections of pipe until end

penetrates roof line. Check to see that

proper clearances are maintained. Extend

chimney by adding sections of double wall

pipe until pipe is minimum of 30" above

highest point of roof cutout. Termination

and chimney must extend a minimum of

36" above highest point where it passes

through roof.

Figure 14 - Roof Opening Measurements

FLASHING INSTALLATION (V6F-8DM

OR V12F-8DM)

Determine flashing to be used with roof open-

ing chart. Slide flashing over pipe until base is

flat against roof. Replace as many shingles as

needed to cover exposed area and flashing

base. Secure in position by nailing through

shingles (see Figure 15, page 11). DO NOT

NAIL THROUGH FLASHING CONE.
Installing Flashing on a Metal Roof

When installing flashing on a metal roof, it

is required that putty tape be used between

flashing and roof. Flashing must be secured

to roof using #8 x 3/4" screws and then sealed

with roof coating to prevent leakage through

screw holes. A roof coating must also be ap-

plied around perimeter of flashing to provide

a proper seal.

FIRESTOP SPACERS (3600FS-8DM-1)

Firestop spacers are required at each point

where chimney penetrates a floor space.

Their purpose is to establish and maintain

required clearance between chimney and

combustible materials. When pipe passes

through a framed opening into a living space

above, firestop must be placed onto ceiling

from below as shown in Figure 12.
They also provide complete separation from

one floor space to another or attic space as

required by most codes. When double wall

pipe passes through a framed opening into

an attic space, firestop must be placed into

an attic floor as shown in Figure 13.

Figure 12 - Firestop Spacer with Living

Space Above Ceiling

Figure 13 - Firestop Spacer with Attic

Space Above Ceiling

PENETRATING ROOF

To maintain a 2" clearance to pipe on a roof with

a pitch, a rectangular opening must be cut.
1. Determine center point where pipe will

penetrate the roof.

2. Determine center point of the roof. Pitch

is the distance the roof drops over a given

span, usually 12". A 6/12 pitch means that

the roof drops 6" for each 12" measure

horizontally down from roof rafters.

3. Use roof opening chart (Figure 14) to

determine correct opening length and

flashing required.

If area above is a living space, install

firestop below framed hole.

If area above is an attic or insulated area,

install firestop above framed hole.

30"

(76.2 cm)

Minimum Measurements

Opening "A"

16

3

/

8

"

(48.3 cm)

2"

(5.1

cm)

2"

(5.1

cm)

2"

(5.1 cm)