Venting installation – FMI (V)B42LI User Manual

Page 11

Advertising
background image

www.fmiproducts.com

109036-01M

11

Nail Only

Outer

Perimeter

of Flashing

Storm Collar

Underlap Shingles

at Bottom

Overlap

Shingles Top

and Sides Only

Figure 15 - Flashing Installation

Figure 16 - Storm Collar

Chimney

Pipe

Waterproof

Caulk

Storm

Collar

Flashing

Storm Collar Installation (SC1)
Place storm collar over pipe and slide down

until it is snug against open edge of flashing

(see Figure 16). Use SC1 for all round

terminations. Apply waterproof caulk around

perimeter of collar to provide a proper seal.

Terminations/Spark Arrestor

Fireplace system must be terminated with

listed round top or chase terminations. In any

case, refer to installation instructions supplied

with termination. Terminations approved for

this fireplace are RT-8DM, RTL -8DM and

RLT-8DM that can be used for flashing or

chase and ET-8DM, ETO-8DM, ETL-8DM

and ETLO-8DM for chase style termination

only. Figure 17 shows an RTL-8DM round

top termination.

CAUTION: Do not seal open-

ings on the rooftop flashing. Fol-

low the installation instructions

provided with the termination

being used.

Flashing

Cone

VENTING INSTALLATION

Continued

Attach Bracket

Tabs to

Outer Pipe

(3 Places)

Secure with

Screws

RTL-8DM Level of Flue

Gas Outlet

Caulk

Collar

Flashing

Underlap Shingles

Bottom Only

Figure 17 - Termination

Overlap

Shingles Top

and Sides

Terminations with 16" slip pipe sections are

available. RTT-8DM, RTTL-8DM and RLTT-

8DM are approved for flashing installations.

When needed, these adjustable terminations

may be used in combination with pipe assem-

bly to achieve correct chimney height.
Note: In the rare instance there is a problem

with side driven rain or wind or chimney is

not drafting properly, an ADS-8DM (Anti-Draft

Shield) can be used with round terminations.

Flue Pipe of

RTL-8DM

Inside Inner

Pipe of

Chimney

CHASE INSTALLATIONS

Instructions for chase installations are includ-

ed with chase style termination chosen. In a

multiple chase installation, be sure to provide

adequate distance between terminations to

prevent smoke spillage from one termination

to another. We suggest that terminations be

separated at least 24", center to center and

stacked at a vertical height difference of 18"

(see Figure 18), page 12.
Note: If a decorative shroud is to be installed,

contact manufacturer for specifications.