FIREPLACE INSTALLATION

Continued

Figure 4 - Mantel Clearances to

Combustible Material

Electrical

Bushing

Electrical

Cover

Plate

Rocker

Switch

Figure 6 - Fan Switch-Electrical Bushing

Electrical

Housing

Wire Nut (3x)

(Not Supplied)

Outer Wrapper

of Fireplace

Electrical Cover

Plate and

Electrical Bushing

Fireplace Chassis

Ground

To Power

Source

Receptacle

(Supplied)

Power Source Wiring

(Not Supplied)

Prewired Receptacle

and Ground

MANTELS

A mantel may be installed if desired (see

Figure 4). Woodwork such as wood trims,

mantels or any other combustible material

projecting from front face must not be placed

within 12" of fireplace opening (and within 9"

of top louver opening). Combustible materi-

als above 12" and projecting more than 1

1

/

2

"

from fireplace must not be placed less than

12" from top opening of fireplace (NFPA STD

211, Sec. 7-3.3.3).
Mantels or any other combustible material

may come up to side edge of black metal face

of fireplace if projection from front face falls

within limits shown in Figure 5.

FAN/BLOWER KIT ASSEMBLY

Fan or blower kit is optional with this fireplace

(for circulating models only). Use of blowers

or fans other than those manufactured by

FMI PRODUCTS, LLC voids warranty. Fan

is operated by pressing rocker switch (see

Figure 6) in lower right hand corner of fireplace

face. Blower is operated by turning control

knob (not shown).
Fan/blower kit electrical connections are

made through electrical cover plate on side

of fireplace a shown in Figure 6.

FIREBOX

SAFE ZONE

Figure 5 - Side Mantel Clearance

Top View of Fireplace

Min. 12" from

Perpendicular Side Wall

1"

0.625" Max.

33°

8"

Wiring Instructions

1. Remove electrical cover plate with bush-

ing from fireplace by removing 2 sheet

metal screws as shown in Figure 6.

2. Slide power source wiring through electri-

cal bushing opening and electrical cover

plate and make all necessary connec-

tions.

3. Slide all wiring connections in electrical

housing as shown in Figure 6.

4. Secure electrical cover plate with screws

previously removed.

Note: Electrical housing and cover plate have

sharp edges. Wear protective gloves.

Sheet

Metal

Screws

12

1

/

4

" Ref.

1

1

/

2

"

Max.

Upper Section

of Circulating

Fireplace

6"

Ref.

9"

Min.

33°

3" Nom.

*Note: Drawing

Not To Scale

Safe Zone For

Projection of

Combustible

Materials

Combustible

Material

15"

Min.

12"

Min.

Fireplace Opening

Top of

Louvered

Opening