iNsTallaTioN

Continued

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an open

flame to check for a leak. Apply

a noncorrosive leak detection

fluid to all joints. bubbles form-

ing show a leak. Correct all leaks

at once.

CAUTION: Make sure exter-

nal regulator has been installed

between propane/LP supply

and fireplace. See guidelines

under Connecting to Gas Sup-

ply, page 13.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance

main gas valve (control valve) and equip-
ment shutoff valve from gas supply piping
system. Pressures in excess of 1/2 psig
will damage heater regulator.

2. Cap off open end of gas pipe where equip-

ment shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.

4. Check all joints of gas supply piping system.

Apply noncorrosive leak detection fluid to
all joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Reconnect fireplace and equipment

shutoff valve to gas supply. Check recon-
nected fittings for leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-

ure 16).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve
for propane/LP gas or opening main gas
valve located on or near gas meter for
natural gas or using compressed air.

3. Check all joints from gas meter to equip-

ment shutoff valve for natural gas or pro-
pane/LP supply to equipment shutoff valve
for propane/LP (see Figures 17 or 18).
Apply noncorrosive leak detection fluid to
all joints. Bubbles forming show a leak.

4. Correct all leaks at once.

Figure 16 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff Valve

Figure 17 - Checking Gas Joints

(Propane/LP Only)

Propane/LP
Supply Tank

Equipment
Shutoff Valve

Gas Valve

Equipment
Shutoff Valve

Gas
Meter

Figure 18 - Checking Gas Joints (Natural

Gas Only)

Gas Regulator or
Gas Control Valve