iNsTallaTioN

Continued

PRESSURE TESTING FIREPLACE GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure

16, page 15).

2. Open main gas valve located on or near

gas meter for natural gas or open pro-
pane/LP supply tank valve.

3. Make sure control knob of fireplace is in

the OFF position.

4. Check all joints from equipment shutoff

valve to gas regulator (Manual-Controlled
Models) or to gas control valve (Remote-
Ready Models) (see Figures 17 or 18,
page 15). Apply noncorrosive leak de-
tection fluid to all joints. Bubbles forming
show a leak.

5. Correct all leaks at once.
6. Light fireplace (see Operating Fireplace,

page 18). Check all other internal joints
for leaks.

7. Turn off fireplace (see To Turn Off Gas to

Appliance, page 20 for Manual-Controlled
Models or page 21 for Remote-Ready
Models).