Command

Description

GC x.x.x.x

Get configuration as HEX records

SC x.x.x.x

Set configuration from HEX records

PI x.x.x.x

Check with Ping if x.x.x.x is alive and reachable

AT

Show the VMSE’s ARP table entries

TT

Shows all the incoming and outgoing TCP connections (used
only with “monitor mode” from Telnet)

NC

Shows the IP configuration of the VMSE

RS

Resets the power on the VMSE

SI x.x.x.x:n.n.n.n

With this command, you can remotely assign an IP address to
another VMSE, where x.x.x.x is the new IP address and
n.n.n.n is the remote VMSE serial number written twice. For
example:

SI194.39.78.234:146.138.146.138

IP address = 194.39.78.234

Remote VMSE serial # (146-138) = 146.138.146.138

NOTE: Since this is obtained by sending broadcast packets,
this IP assignment cannot be done over the routers.

QU

Quit - exit diagnostics mode

Command result codes:

0

OK, no error

1

No answer from remote device

2

Cannot reach remote device or does not answer

8

Wrong parameter(s)

9

Invalid command

Firmware Download Using Serial Port

Downloading is done in monitor mode. Once the VMSE is in monitor mode, by
using “DL” command, the VMSE will wait for the firmware image in Intel Hex
format. This must only be sent through the serial interface. When the end record is

Advertising