03 i, Chapter 7 global meter setup, 0, f – GE EPM 3000P User Manual

Page 31: 3 - p, 5 - t, 1 & 2 (o, Must have communication option), Ge industrial systems

Advertising
background image

Chapter 7 Global Meter Setup

7.5 G

ROUP

0, F

UNCTION

3 - P

ROGRAMMING

P

ROCEDURE


Ö

To change the SYSTEM CONFIGURATION SWITCH settings, follow these steps:

NOTE: PRESS MAX/MIN/LIMITS, AT ANY TIME, BEFORE STORING THE LAST DIGIT OR SWITCH.

MAX

AC VOLTS

A B C N

AC AMPS

MAX/MIN

LIMITS

VOLTS

PRINT
PROG

PHASE

NEXT

0.

AMPS

B C A

I I I

A B C

N N N

I I I

A B C

LM2

LM1

MIN

MAX

AC VOLTS

A B C N

AC AMPS

MAX/MIN

LIMITS

VOLTS

PRINT
PROG

PHASE

NEXT

03.0

AMPS

B C A

I I I

A B C

N N N

I I I

A B C

LM2

LM1

MIN

_

_

_

Step 1:

a. Enter Group Level of Programming Mode,

(see Chapter 6).

b. Press MAX/MIN/ LIMITS until 0. appears in

upper display.

c. Press VOLTS to activate the Group.

Ö

03.0 appears in upper display.

Ö

Lower display indicates current PACK 0 Switch

Settings.

MAX

AC VOLTS

A B C N

AC AMPS

MAX/MIN

LIMITS

VOLTS

PRINT
PROG

PHASE

NEXT

03 I

AMPS

B C A

I I I

A B C

N N N

I I I

A B C

LM2

LM1

MIN

_ _

_

MAX

AC VOLTS

A B C N

AC AMPS

MAX/MIN

LIMITS

VOLTS

PRINT
PROG

PHASE

NEXT

03. I

AMPS

B C A

I I I

A B C

N N N

I I I

A B C

LM2

LM1

MIN

_

_

_

Step 2:

a. Press PRINT/PROG until desired PACK appears.

b. Press VOLTS to begin Data Entry Sequence.


Ö

Three dashes appear in lower display.

Step 3:

a. Press PRINT/PROG to toggle the segments UP or

DOWN for desired setting.

b. Press VOLTS to store


See Chapter 12 to Exit.



7.6 G

ROUP

0, F

UNCTIONS

4-5 - T

IME

D

ELAY FOR

R

ELAYS

1 & 2 (O

PTION

NL)

The EPM3000P can be equipped with a relay option. Two relays are included in this option. The relays can be used in
computer controlled or dedicated alarm options.

COMPUTER
CONTROLLED

The relays can be locked or unlocked through a computer

(must have communication

option).

DEDICATED ALARM


The relays can be locked or unlocked using the meter's keypad or its measured inputs.
The computer cannot change the state of the relay.

Under GROUP 0, FUNCTIONS 4-5, time delay for the Relays 1 or 2 can be set between 0 - 255 seconds. This allows
conditions to exist for a specified time period before the relay or alarm activates. If a time greater than 255 seconds is
entered, the meter defaults to the maximum value of 255 seconds.

26

GE Industrial Systems

Advertising