Chapter 10, Rogramming, Roup – GE EPM 3000P User Manual

Page 39: Imits, Elays, Group 4: set limits for volts/amps

Advertising
background image

CHAPTER 10

P

ROGRAMMING

G

ROUP

4: S

ET

L

IMITS

& R

ELAYS

GROUP 4 contains LM1 and LM2 set limit values for the voltage and amperage scale allowing the user to program
the limits for the following Groups: VOLTS phase-to-neutral, VOLTS phase-to-phase, AMPS A, B, C, and AMPS
neutral.

D

IAGRAM

10.1: E

XAMPLE OF

LM1/LM2 S

ET

L

IMITS

, V

OLTS AND

A

MPS

LM1 AND LM2 SET LIMITS

PHASES

CURRENT

0

20

40

60

80

100

120

A B C

120

40

LM1 is triggered

LM2 is triggered

50

(AMPS)

80

LM1 SET TO

TRIGGER ABOVE

100 AMPS.

LM2 SET TO

TRIGGER BELOW

50 AMPS.



10.1 T

RIP

R

ELAY


The EPM3000P has two Relays. These relays are linked through the program to Set Limits LM1 and LM2. The user
can program above or below set limits for every reading. When a measurement exceeds a particular value, the set
limit triggers and alerts the user. Each relay is programmed to a separate delay time (see Chapter 8).

NOTE: E

ACH LIMIT CAN BE PROGRAMMED TO TRIGGER THE TWO INTERNAL

F

ORM

C

DRY CONTACT RELAYS FOR ALARM OR

SECONDARY PROTECTION

.


GROUP 4: SET LIMITS FOR VOLTS/AMPS

T

ABLE

10-0: G

ROUP

4 P

ROGRAMMING

F

ORMAT

FUNCTION NUMBER

FUNCTION

0.

LM1/LM2 Set Limits for Volts AN,BN,CN

1.

LM1/LM2 Set Limits for Volts AB,CB,CA

2.

LM1/LM2 Set Limits for Amps A,B,C

3.

LM1/LM2 Set Limits for Amps Neutral

E.

Exit Programming GROUP 4


NOTE: I

N

T

ABLE

10-0,

ALL FUNCTIONS HAVE A TWO PART ENTRY

.



Part 1
: The first switch sets the limit to trip either above or below the limit value.

The second switch sets whether Relay 1 will trip when the condition occurs.

The third switch sets whether Relay 2 will trip when the condition occurs.


Part 2: The second part is the Limit Value.

34