CHAPTER 11

P

ROGRAMMING

G

ROUP

7: P

HASE

R

EVERSAL

& P

HASE

I

MBALANCE

S

ET

L

IMITS

/R

ELAYS

11.1 V

OLTAGE

P

HASE

R

EVERSAL AND

P

HASE

I

MBALANCE


The set limit alerts the user of an unbalanced or a reversed phase in a Three-phase System. The EPM3000P has two
options for this purpose.

PHASE REVERSAL:

Activates when a reversed phase enters the EPM3000P’s metering system.

PERCENT PHASE IMBALANCE:
Activates when the user’s present value percent phase imbalance is exceeded. For example: an unbalanced Three-
phase System.

D

IAGRAM

11.1: E

XAMPLE OF

S

ET

L

IMITS

1 0 :0 0 A M

1 1 :0 0 A M

L im its N o t

T rig g e re d

L im its T rig g e re d

P H A S E

IM B A L A N C E

(% )

1 0 .0 %

T H R E E P H A S E S Y S T E M IM B A L A N C E





11.2

T

RIP

R

ELAY


NOTE: T

HE

-NL

OPTION MUST BE PURCHASED TO HAVE RELAYS TRIGGERED FROM

L

IMIT

C

ONDITIONS

.


The EPM3000P has two Relays. These relays are linked through the program to Set Limits LM1 and LM2. The user
can program above or below set limits for every reading. When a measurement exceeds a particular value, the set
limit triggers and alerts the user. Each relay has provisions for a separate delay time (see Chapter 8).

c

TRIP RELAY I

Whether to trip Relay 1.

d

TRIP RELAY II

Whether to trip Relay 2.

e

LEVEL

The level at which the warning mechanism trips. Percentage of voltage imbalance is
entered for setup level.
-OR-

f

ENABLE/DISABLE

In the event of Phase Reversal, indicates whether to enable or disable phase reversal
detection.




T

ABLE

11-0: G

ROUP

7 P

ROGRAMMING

F

ORMAT

FUNCTION NUMBER

FUNCTION

0.

Voltage Phase Reversal Detection

1.

Voltage Phase Imbalance

E.

Exit Programming GROUP 7

38

GE Industrial Systems