CHAPTER 9

P

ROGRAMMING

GROUP 2: M

ETER

C

ALIBRATION

9.1 S

TANDARD

C

ALIBRATION

WARNING

- R

EAD THIS

S

ECTION

C

AREFULLY

B

EFORE

P

ROCEEDING


Calibration does not need to be accomplished to change CT or PT ratios. (See GROUP 1).


Meter calibration cannot be performed if the meter is installed for service. The sensing must be

connected to a power supply with variable voltage and separate current outputs.


The calibration procedure requires highly accurate and stable input signals. Incorrect

readings result from improper calibration procedures. If unsure, return unit to the factory for

calibration.

BEFORE calibrating any channel, make note of its Full Scale Setting (see Ch. 8). Set the Full

Scale in accordance with Table 9-1 for calibration. Restore original Full Scale Setting when

calibration is completed.


The first function in GROUP 2 (STD.CORR) is NOT to be changed by the user. Please make

note of the value here (

) before using any other function in this Group. If the STD.CORR

value is inadvertently lost or changed, contact the factory for assistance.


All sensitive electronic measuring devices drift slightly over time, requiring periodic calibration. We recommend
returning the meter to the factory on a yearly basis.


T

ABLE

9-0: G

ROUP

2 P

ROGRAMMING

F

ORMAT

FUNCTION NUMBER

FUNCTION

P. Standard

Correction.

Factory Procedure only.

0.

High End Calibration, VOLTS AN

1.

High End Calibration, VOLTS BN

2.

High End Calibration, VOLTS CN

3.

High End Calibration, AMPS A

4.

High End Calibration, AMPS B

5.

High End Calibration, AMPS C

6.

Low End Calibration, AMPS A

7.

Low End Calibration, AMPS B

8.

Low End Calibration, AMPS C

E.

Exit Programming GROUP 2




The Full Scale and Calibration values should be equal during the calibration procedure. The meter may be rescaled
without calibrating by changing the full scale in GROUP 1, FUNCTION 0 or 1. (See Table 9-1)


T

ABLE

9-1: S

OURCE

, F

ULL

S

CALE AND

V

ALUE

S

ETTINGS FOR

C

ALIBRATION

CALIBRATION TYPE/

RANGES

CALIB. SOURCE

NECESSARY

FULL SCALE SETTING

CALIBRATION VALUE

VOLTS 120/208V

120V

120V

120

VOLTS 277/480V

300V

300V

300

VOLTS 4/1 PT

120V

480V

480

VOLTS 60/1 PT

120V

7.20KV

7.20

AMPS Hi End 1000/5 CT

5A

1000A

1000

AMPS Hi End 5000/5 CT

5A

5.00KA

5.00

AMPS Lo End 1000/5 CT

2.5A

500

AMPS Lo End 5000/5 CT

2.5A

2.50


31

GE Industrial Systems