EXAMPLE 1:

Relay 1 will be “SET” once the reading exceeds 5.00 amps. Relay 1 will be “RESET” once the reading
falls below 5.00 amps.

5 . 0 0 A

0 A

R E S E T

L 1

S E T

N O P O W E R T O T H E U N I T

R E S E T


1. Enter in GROUP 0, FUNCTION 4, Segment C and D: UP, DOWN
2. Enter in GROUP 4, FUNCTION 2, LIMIT 1, Segments B, C, and D: UP, UP, DOWN



EXAMPLE 2: NORMALLY RESET - NON-EVENT CONDITION WILL RESET RELAY

Relay 1 will be “SET” if the instantaneous reading for amps is below 4.00 amps or above 5.00 amps.
Under all other conditions the relay will be “RESET”.

NOTE: U

NDER THIS SETUP THE RELAY WILL

NOT

ACT AS A PROTECTIVE SWITCH

.

4 . 0 0 A

5 . 0 0 A

0 . 0 0 A

S E T

S E T

L M 2

L M 1

R E S E T

N O P O W E R T O T H E U N I T

R E S E T


P

ROGRAMMING

S

TEPS

:

1. Enter in GROUP 0, FUNCTION 4, Segments C and D: UP, UP
2. Enter in GROUP 4, FUNCTION 2, LIMIT 1, Segments: B, C, and D: UP, UP, DOWN. Value: 5.00
3. Enter in GROUP 4, FUNCTION 2, LIMIT 2, Segments: DOWN, UP, DOWN. Value: 4.00

27