Chapter 2 Electrical Installation

2.5 E

LECTRICAL

C

ONNECTION

I

NSTALLATION

Choose the diagram that best suits your application and maintain the polarity. Follow the outlined
procedure to verify correct connection.

NOTE:
T

HE NEUTRAL READING IS CALCULATED FROM THE SUM OF THE

3

PHASES OF CURRENT

. H

IGH NEUTRAL

CURRENT INDICATES REVERSE

CT

POLARITY

.



LISTING OF CONNECTION DIAGRAMS

NOTE: S

EE PHASE REVERSAL IF A MESSAGE OF

PH

APPEARS AFTER INSTALLATION

.



I

Three-Phase, Three-Wire System Delta with Direct Voltage and CTs.


II

Three-Phase, Three-Wire Open Delta with two CTs and two PTs.

(Open Delta System Installation should only be used if the electrical system is a 3-wire OPEN

DELTA. Open Delta can be enabled or disabled in Programming Group 0, Function 3.)


III

Three-Phase, Three-Wire Open Delta with three CTs and two PTs.

(Open Delta System Installation should only be used if the electrical system is a 3-wire OPEN

DELTA. Open Delta can be enabled or disabled in Programming Group 0, Function 3.)


IV

Three-Phase, Four-Wire System Wye with Direct Voltage and CTs.


V

Three-Phase, Four-Wire System Wye with CTs and PTs.


VI

Single Phase System


VII

Dual Phase System

4

GE Industrial Systems