Generac Power Systems Recreational Vehicle Generator 5413 User Manual

Page 15

Advertising
background image

Section 3

INSULATION RESISTANCE TESTS

vents that will not attack such materials.

Use a soft brush or cloth to apply the solvent. Be

careful to avoid damage to wire or winding insulation.

After cleaning, dry all components thoroughly using

moisture-free, low-pressure compressed air.

*

DANGER!: DO NOT ATTEMPT TO WORK

WITH SOLvENTS IN ANY ENCLOSED AREA.
PROvIDE ADEQUATE vENTILATION WHEN
WORKING WITH SOLvENTS. WITHOUT
ADEQUATE vENTILATION, FIRE, ExPLOSION
OR HEALTH HAZARDS MAY ExIST . WEAR
EYE PROTECTION. WEAR RUBBER GLOvES
TO PROTECT THE HANDS.

CLOTH OR COMPRESSED AIR:
For small parts or when dry dirt is to be removed, a

dry cloth may be sufficient. Wipe the parts clean, then

use low pressure air at 30 psi (206 kpa) to blow dust

away.

BRUSHING AND VACUUM CLEANING:
Brushing with a soft bristle brush followed by vacuum

cleaning is a good method of removing dust and dirt.

Use the soft brush to loosen the dirt, then remove it

with the vacuum.

STATOR INSULATION RESISTANCE

GENERAL:
Insulation resistance is a measure of the integrity of

the insulating materials that separate electrical wind-

ings from the generator’s steel core. This resistance

can degrade over time due to the presence of con-

taminants, dust, dirt, grease and especially moisture.
The normal insulation resistance for generator wind-

ings is on the order of “millions of ohms” or “mego-

hms”.
When checking the insulation resistance, follow the

tester manufacturer’s Instructions carefully. Do NOT

exceed the applied voltages recommended in this

manual. Do NOT apply the voltage longer than one

(1) second.

*

CAUTION!: DO NOT connect the Hi-Pot Tester

or Megohmmeter test leads to any leads that
are routed into the generator control panel.
Connect the tester leads to the Stator or Rotor
leads only.

STATOR SHORT-TO-GROUND TESTS:
See Figure 3-2. To test the Stator for a short-to-ground

condition, proceed as follows:
1. Disconnect and Isolate all Stator leads as follows:

a. Disconnect sensing leads 11S and 22S from

the voltage regulator.

b. Disconnect excitation winding lead No. 6 from

the voltage regulator.

c. Disconnect excitation lead No. 2 from the volt-

age regulator (VR).

e. At the main circuit breakers, disconnect AC

power leads No. 11 and 33.

f. At the 4-tab ground terminal (GRD2), discon-

nect Stator power leads No. 22 and 44.

2. When all leads have been disconnected as out-

lined in Step 1 above, test for a short-to-ground

condition as follows:

a. Connect the terminal ends of all Stator leads

together (11S, 22S, 11, 22, 33, 44, 2, & 6).

b. Follow the tester manufacturer’s instructions

carefully. Connect the tester leads across

all Stator leads and to frame ground on the

Stator can. Apply a voltage of 1500 volts. Do

NOT apply voltage longer than one (1) sec-

ond.

If the test indicates a breakdown in insulation, the

Stator should be cleaned, dried and re-tested. If the

winding fails the second test (after cleaning and dry-

ing), replace the Stator assembly.

TEST BETWEEN ISOLATED WINDINGS:
1. Follow the tester manufacturer’s instructions care-

fully. Connect the tester test leads across Stator

leads No. 11 and 2. Apply a voltage of 1500 volts-

DO NOT ExCEED 1 SECOND.

2. Repeat Step 1 with the tester leads connected

across the following Stator leads:

a. Across Wires No. 33 and 2.
b. Across Wires No. 11 and 33.
c. Across Wires No. 11 and 2.

If a breakdown in the insulation between isolated

windings is indicated, clean and dry the Stator. Then,

repeat the test. If the Stator fails the second test,

replace the Stator assembly.

TEST BETWEEN PARALLEL WINDINGS:
Connect the tester leads across Stator leads No. 11

and 33. Apply a voltage of 1500 volts. If an insula-

tion breakdown is indicated, clean and dry the Stator.

Then, repeat the test between parallel windings. If the

Stator fails the second test, replace it.

Page 13

Advertising