Generac Power Systems Recreational Vehicle Generator 5413 User Manual

Page 37

Advertising
background image

Section 6

TROUBLESHOOTING FLOWCHARTS

Page 35

REPLACE

PRINTED CIRCUIT

BOARD

INSTALL NEW
7.5 AMP FUSE

CHECK THAT FUSE

HOLDER IS NOT

GROUNDED

CHECK WIRE 15

FOR SHORT TO

GROUND

CHECK REMOTE

HARNESS WIRE 15

FOR SHORT TO

GROUND

CHECK WIRE 56

FOR SHORT TO

GROUND

CHECK WIRE 90

FOR SHORT TO

GROUND

CHECK CHOKE

SOLENOID AND

STARTER

CONTACTOR

RELAY

STARTER CONTACTOR

RELAY PIN LOCATION

J1-1 TEST TO GROUND

CHOKE SOLENOID
PIN LOCATION J1-2

TEST TO GROUND

REMOVE WIRE 15

FROM JI HARNESS

CONNECTOR.

DOES FUSE BLOW?

(SEE NOTE A)

PERFORM RESISTANCE TESTS ON FUEL PUMP, FUEL SOLENOID,
CHOKE HEATER AND REMOTE HARNESS WIRE 14 (SEE * BELOW).
ALSO CHECK WIRE 14 TO EACH COMPONENT FOR SHORT TO GROUND.

* CHECK FOR CONTINUITY TO FRAME GROUND. CONNECT ONE TEST
LEAD TO THE POSITIVE WIRE FOR EACH COMPONENT. CONNECT THE
OTHER TEST LEAD TO FRAME GROUND. RESISTANCE SHOULD BE
MEASURED. IF CONTINUITY “0” IS MEASURED TO GROUND, THAT
COMPONENT OR WIRE IS SHORTED.
ALSO, REFER TO THE INDIVIDUAL TESTS FOR EACH COMPONENT IN
SECTION 7, UNDER “PROCEDURE – SHORT TO GROUND”.

NOTE A:
Disconnect harness from engine controller
circuit board.
Gently bend red tabs outward and remove red
plastic pin guide.
Using a small flathead screwdriver, slide black
retainer tabs out away from Wire 15 pin
(orange).
Gently push pin out of harness and pull wire
out from back of plug, noting it’s location for
reinstallation later.
Replace red pin guide and plug J1 harness
back into engine controller circuit board.
Replace fuse.
If fuse does not blow, replace engine controller
circuit board.
If fuse still blows, continue to next section of
Problem 10 flow chart.

DISCONNECT JI HARNESS

FROM ENGINE CONTROL-
LER CIRCUIT BOARD AND

CHECK WIRE 14 FOR
SHORT TO GROUND.

IS CONTINUITY PRESENT?

FUSE BLOWS UPON

INSTALLATION

FUSE IS GOOD BUT

BLOWS WHEN START-

STOP SWITCH IS

PRESSED

REPAIR OR
REPLACE
COMPONENT
OR WIRE

REPLACE COMPONENT OR WIRE

PASS

YES

YES

FAIL

FAIL

FAIL

NO

NO

REPLACE HOLDER

Problem 10 – 7.5A (F1) Fuse Blowing