Test 4 – fixed excitation test/rotor amp draw – Generac Power Systems Recreational Vehicle Generator 5413 User Manual

Page 39

Advertising
background image

Section 7

DIAGNOSTIC TESTS

4. If no movement is seen in Step 3 remove the con-

trol panel cover. Verify the six pin connector (j2)

on the Printed Circuit Board is seated properly,

remove the connector and then replace it and test

again. Verify the dip switches are correctly set.

NOTE: The dip switches on the Printed Circuit

Board are factory set in the “OFF” or dOWN posi-

tion. Refer to Figure 5.2 on Page 22.
5. If problem continues remove six pin connector

(j2) from Printed Circuit Board. Set Volt meter to

measure ohms. Carefully measure from the end

of the six pin harness as follows:

RED

EMPTY

YELLOW

BROWN

ORANGE

BLACK

Figure 7-2. Six Pin J2 Connector Wire Colors

NOTE: Press down with the meter leads on the

connectors exposed terminals, do not probe into

the connector.

a. Connect one meter lead to Red, connect the

remaining test lead to Orange, approximately 10

ohms should be measured.

b. Connect one meter lead to Red, connect the

remaining test lead to Yellow, approximately 10

ohms should be measured.

c. Connect one meter lead to Red, connect the

remaining test lead to Brown, approximately 10

ohms should be measured.

d. Connect one meter lead to Red, connect the

remaining test lead to Black, approximately 10

ohms should be measured.

e. Connect one meter lead to Red, connect the

remaining test to the stepper motor case. No

resistance should be measured (“Infinity” or

Open).

RESULTS:
1. If the stepper motor fails any part of Step 5

replace the stepper motor.

2. If the stepper motor passes all steps replace the

Printed Circuit Board.

TEST 4 – FIxEd ExCITATION TEST/ROTOR

AMP dRAW

DISCUSSION:
The fixed excitation test consists of applying bat-

tery voltage (12 VDC) to the Rotor windings. This

allows that portion of the excitation circuit between

the Voltage Regulator and the Rotor (including the

Rotor itself) to be checked as a possible cause of the

problem. When battery voltage is applied to the Rotor,

the resulting magnetic field around the Rotor should

induce a Stator power winding voltage equal to about

one-half the unit’s rated output voltage.

6

0

4

13 13

2

4

22S

11S

15

JUMPER WIRE

WIRES 4 REMOVED FROM
VOLTAGE REGULATOR

VOLTAGE
REGULATOR

FUSE HOLDER (F1)

RED TEST LEAD

BLACK TEST LEAD

Figure 7-3. – Fixed Excitation Test, Step A

PROCEDURE:
1. Disconnect Wire 4 from the Voltage Regulator

(VR). (Third terminal from the right side of VR).

2. Connect a jumper wire to Wire 4 and to the 12 volt

fused battery positive supply Wire 15, located at

the fuse (F1) holder (see Figure 7-3).

NOTE: during this test, Wire 15 must remain con-

nected to the fuse (F1) holder.
3. Set the VOM to measure AC voltage.

Page 37