Test 5 – check field boost, Test 6 – test stator dpe winding – Generac Power Systems Recreational Vehicle Generator 5413 User Manual

Page 41

Advertising
background image

Section 7

DIAGNOSTIC TESTS

6

0

4

13 13

2

4

22S

11S

15

WIRES 4 REMOVED FROM
VOLTAGE REGULATOR

VOLTAGE
REGULATOR

FUSE HOLDER (F1)

RED TEST LEAD

BLACK TEST LEAD

1.11 Amp

Figure 7-6. – Fixed Excitation Test, Step D

7. Re-connect Wire 11S and Wire 22S to the Voltage

Regulator.

8. Remove the jumper wire between Wire 4 and 12

volt supply.

9. Set the VOM to measure DC amps.
10. Connect one meter test lead to the 12 volt fused

battery supply Wire 15, and connect the other

meter test lead to Wire 4 (should still be discon-

nected from the VR). See Figure 7-6.

11. Start the generator. Measure the DC current.

Record the rotor amp draw.

12. Stop the generator. Re-connect Wire 4 to the

Voltage Regulator.

RESULTS:
AC Voltage across Wires 2 and 6 = _________

AC Voltage across Wires 11S and 22S = _________
Proceed to “TEST 4 RESULTS” (top of page 40).

Match all results to corresponding column in the chart.

The column letter refers to the Problem 4 flow charts

on pages 28 and 29.

TEST 5 – CHECk FIELd BOOST

DISCUSSION:
Field boost current is delivered to the Rotor only while

the engine is being cranked. This current helps ensure

that adequate “pickup” voltage is available to turn the

Voltage Regulator on and build AC output voltage.

Loss of the field boost function may or may not result

in a problem with AC output voltage. If the Rotor’s

residual magnetism is sufficient to turn the Regulator

on, loss of the function may go unnoticed. However, if

the Rotor’s residual magnetism is not enough to turn

the Regulator on, loss of field boost can result in fail-

ure of the unit to generate an output voltage.

PROCEDURE:
1. Set VOM to measure DC voltage.
2. Disconnect Wire 4 from the Voltage Regulator and

connect the positive (+) test lead to it. Connect the

negative (-) test lead to a clean frame ground.

3. Set the Start-Stop Switch to “START.” During

cranking only, measure DC voltage. It should

read 3-5 VDC. Reconnect Wire 4 to the Voltage

Regulator.

RESULTS:
1. If field boost checks good, replace the Voltage

Regulator.

2. If voltage is not measured, replace the PCB.

REGULATOR

VOLTAGE

2

2

0

6

22S

4

11S

6

0

4

22S

11S

BA

4

0

FIELD

Figure 7-7. – The Field Boost Circuit

TEST 6 – TEST STATOR dPE WINdINg

DISCUSSION:
An open circuit in the Stator excitation windings will

result in a loss of unregulated excitation current to the

Voltage Regulator. The flow of regulated excitation cur-

rent to the Rotor will then terminate and the unit’s AC

output voltage will drop to a value that is commensurate

with the rotor’s residual magnetism (about 5 - 12 VAC).