Martin Fireplaces 400BWBIA User Manual

Page 11

Advertising
background image

61D0008

11

8"

Min.

6" Min. Brick

or Stone

from Top

of Platform

Brick or Stone Hearth Extension

52" (400 Models)

66" (500 Models)

16" Min.

(400 Unit)

20" Min.

(500 Unit)

8"

Min.

6" Min. Brick

or Stone

from Top

of Platform

Brick or Stone Hearth Extension

52" (400 Models)

66" (500 Models)

16" Min.

(400 Unit)

20" Min.

(500 Unit)

FLOOR PROTECTION

INSTALLING FIREPLACE ON COMBUSTIBLE FLOOR

If fireplace is installed on a combustible floor, protect the floor area either side of the fireplace opening and in the front

with an insulating non-combustible hearth extension. (16" [400 unit] or 20" [500 unit] minimum in front of fireplace and

8" minimum on both sides. See Figures 6 through 12.

Fireplace

Platform May Extend Under Hearth
Extension if Desired

Platform

(If Necessary)

Metal Safety Strip Must Be
Use if Unit Is Placed on
Combustible Floor

Metal Safety Strip

Must Be Use if

Unit Is Placed on

Combustible Floor

Figure 6 - Installing Floor

Protection (Circulating Model)

Figure 6 - Installing Floor Protection (Radiant Model)

Fireplace

Hearth Extension Clearances & Width

400 Unit

500 Unit

On Both Sides

8" Min.

8" Min.

Front of Fireplace 16" Min.

20" Min.

Extension Width

52"

66"

Note: Do not block the side air

vents or air inlet louvers on
the lower front of the fireplace
with hearth extension.

Air vents and air inlet louvers allow

necessary cooling air around the fire-

place. Determine the finished height of

the hearth extension to be used. Raise

the fireplace on a platform, if necessary,

to prevent blocking of air openings and

lower louvered panel.
Note: No platform is needed if

hearth extension does
not exceed 1" thick for
circulating units or 6½" for
radiant units.

Air Vents — DO NOT BLOCK