ELBOW INSTALLATION

(CONTINUED)

3. The number of elbows per chimney allowed are as follows:

If the total height of the fireplace and chimney is 13' 6"

or more, two (2) elbows may be used.

If the total height of the fireplace and chimney is 20' or

more, four (4) elbows may be used.

4. Inclined portions of chimney is often used as storage.

Enclose the inclined portions of chimney that pass through

living spaces to avoid contact with and possible damage

to chimney. Maintain minimum air space of 2" between

chimney and enclosing. See Figures 22 and 23.

CHIIMNEY INSTALLATION

Figure 22 - Installing Chimney with Total Height of

Fireplace and Chimney 13' or More

Figure 23 - Installing Chimney with Total

Height of Fireplace and Chimney 20' or More

Continue Chimney to

Proper Height and

Install Round

Chimney Cap or

Chimney

Housing

Center Line

Storm Collar

Flashing

Roof

Center Line

SF Firestop Spacer

— 2" min. Air

Space Clearance to

Combustibles

SF Firestop Spacer

2" min. Air Space

Clearance to

Combustibles

Vertical Chimney

Enclosure

Support Straps

Support

Straps

Note: Two (2)
elbows may be
used when total
installation height
is more than 13'.

Vertical Chimney

Enclosure

Note: Chimney
must be enclosed
in accessible
areas

Support Straps

Note: Do not let support
straps penetrate firestop

Note: Vertical
chimney enclosure
is recommend.
Diagonal chimney
enclosure is
acceptable.

Diagonal
Chimney

Enclosure

Support Strap

5. The length of inclined portion of chimney between elbows must not exceed 6' if elbows are not supported.

The length of inclined portion of chimney between elbows must not exceed 20' if elbows are supported every 6' with

metal support straps.

6. When enclosing the elbows and inclined portions of the chimney, enclosing materials must be installed vertically to

maintain the required 2"minimum air space clearance to the chimney at the extremities of the offset. It is best that enclos-

ing material not follow inclined portions of chimney.

Note: Four (4) elbows may be used when total installation
height is more than 20'. Four (4) is the maximum number of
elbows allowed.