Vermont castings ewf36a, Hearth installation, Common materials and factors – MHP EWF36A User Manual

Page 16

Advertising
background image

16

Vermont Castings EWF36A

20005167

Examples of wall shield insulation:

1. Manville - CERAFORM 126, K=.27,

1/2 inches thick
2. EH2416, K = .458,

1 inch thick required.

hearth installation

A hearth extension is required to protect a combustible

floor in front of the fireplace. Refer to Figure 26 for mini-

mum dimensions and mounting detail.
NoTE: hearth Extension must not cover the air

inlet opening of a fireplace.
The hearth extension described in Figure 26 must be a

durable noncombustible material with a minimum (total)

Rt value of 1.09; refer to Figure 24 for examples. The

overall height (above a combustible floor), depth and

width must be as indicated, with the extension centered

to the fireplace opening.
The top of insulation must be covered with a non-com-

bustible decorative covering

or a piece of .018” mini-

mum sheet metal, to protect hearth extension material.

(Fig. 26)
Secure the hearth extension to the floor to prevent

shifting, using trim molding or other similar means at

three (3) outer edges. Seal crack between the fireplace

hearth and hearth extension with a noncombustible

material. (Figs. 25 and 26)
WARNiNg: hearth extension must be installed in

accordance with Figure 25. Top of hearth extension

must be level with bottom of fireplace.
Alternate noncombustible materials may be used

providing the (total) thermal resistance (Rt value) of the

alternate material employed is greater than or equal to

R = 1.09 Thermal resistance (R) or thermal conductivity

(K), may be obtained from manufacturer of the material.

Factors are related by the formula K = 1/R. (Fig. 24)
T = given thickness

R = thermal resistance for a given thickness (T)

K = thermal conductivity

Noncombustible material with a lower R value may

be used, provided thickness of material is sufficiently

greater to maintain an equivalent (total) thermal resis-

tance (Rt).

Example of Determining hearth Extension

Equivalents

To determine the thickness required for any

new mate-

rial:

FP550

BR/BC - SEALING

DETAILS

9/29/97

Wall Covering

2 x 4 Header - Do not

notch at standoffs

Noncombus-

tible Decorative

Facing

Seal all cracks

between fireplace sur-

round (steel) and wall

materials with noncom-

bustible material.

Cast Front

Noncombustible

Decorative Cover-

ing

Safety Strips - Must be

overlapped 1/2” minimum

FP1202

Fig. 25 Sealing gaps.

NoTE: No

material

may cover

black cast

face.

COMMON MATERIALS AND FACTORS

MATERIAL

K*

R

MINIMUM

THICKNESS

EH2416

Common Brick

0.916

5.0

2.18 1.0 in.**

0.10 5.46 in.**

(CFM Corporation)

R Value is for 1/2 inch.

* Units of K = BTU/SQ FT/HR/˚F/IN

** Thickness of Listed Material

FP533ADD

Addendum

6/1/99 djt

8/4/99 changed .2 to .1

one inch to 1/2 inch djt

FP533ADD

Fig. 24 Hearth extension material factors.

NEW

K of new material (per inch)

thickness

required =

X of listed

thickness K of listed material (per inch) material

Example for common brick

T (new) = 5.0/0.458 x 0.50 in. =

5.46 in. (new required

thickness).