Page 7: Mounting the fireplace, Planning the chimney run

Advertising
background image

7

Vermont Castings EWF36A

20005167

planning information

Determine how the chimney will be run, length of run

and chimney components required to complete the

job. (Fig. 4)

Never install a chimney below minimum

heights.
In planning a chimney system, it is important to know:

1. The height of a chimney is measured from the hearth

to the exit point on the termination.

2. A chimney cannot be offset more than 30° from a

vertical plane.

3. A chimney may run straight up or it may be neces-

sary to offset it to avoid obstructions.

4. The maximum length of an angled run (total chimney

system) is 20 feet.

5. No more than 2 offsets (4 total 30° elbows in U.S./or

2 total 45° elbows in Canada) per fireplace may be

used.

6. A guy wire stabilizer is required for chimneys extend-

ing more than 6’ (1.8m) above a roof line.

The Ten Foot Rule

Major U.S. building codes specify a minimum chimney

height above the roof top. The “Ten Foot Rule” is a fire

safety rule and not a draft rule. To ensure proper draft,

it is recommended that you always meet or exceed the

“Ten Foot Rule,” especially when installing a termination

on a high pitch roof. (Fig. 5)
The key points of the “Ten Foot Rule” are:
1. If the horizontal distance from the chimney to the

peak of the roof is 10’ (3m) or less, the top of the

chimney must be at least 2’ (610mm) above the peak

of the roof, but never less than 3’ (914mm) in height

above the highest point where it passes through the

roof.

2. If a horizontal distance from the chimney to the peak

of the roof is more than 10’ (3m), a chimney height

reference point is established that is on the surface

of the roof a distance of 10’ (3m) from the chimney in

a horizontal plane. The top of the chimney must be

at least 2’ (610mm) above the reference point, but

never less than 3’ (914mm) in height above the high-

est point where it passes through the roof.

2' Min.

2' Min.

3'

Min.

0 To 10'

3'

Min.

0 To 10'

AC246

4/1/96

Reference

Point

AC246

Fig. 5 Ten Foot Rule illustration.

Planning an installation is very important to ensure

safety and to save time and money. An installer must

predetermine where a fireplace will be set and how the

chimney system will be run.
NoTE: If installing the EWF36CFTK at a later date and

if the hearth is being raised in front of the firepalce, the

fireplace must be raised to the same height.

Mounting the Fireplace

The fireplace is shipped with lifting handles attached to

each side with lifting straps.

NoTE: The lifting straps

are intended for ligting unit off of the skid and final po-

sitioning. Unit should remain on skid until final position-

ing. After fireplace is in position, the lifting handle and

straps may be removed or left in place.
A fireplace may only be mounted on the following sur-

faces:
1. A flat combustible surface.

2. A raised wooden platform.

3. A concrete block or other solid object placed beneath

each of the four (4) corners of the fireplace.

The fireplace

must be spaced 1” from a combustible

back wall and 1” from a combustible side wall or sup-
port. (Page 13, Fig. 17)

planning the chimney Run

L1

L1

LT

TOTAL

LENGTH

(LT)

INSTALLED

LENGTH

(L1)

56O

"

56O

"

56O

"

56O

"

56O

"

56O

"

56O

"

56O

"

FP288A

MBUF-INSTALLED LENGTH

Triple wall

1/28/99 djt

TRIPLE

WALL

81

818

83

84

FP288a

Fig. 4 Installed lengths of chimney sections.