Section 3

Operation

Part Number 000001130 12/08

3-5

WATER LEVEL CHECK

Check the water level while the ice machine is in the ice
mode and the water pump is running. The correct water
level is 1/4”(6.3mm) to 3/8” (9.5mm) below the top of the
standpipe a line in the water trough indicates the correct
level.

Water Level

The float valve is factory-set for the proper water level. If
adjustments are necessary:

1. Verify the ice machine is level (see page 2-4).

2. Remove the siphon cap from the standpipe.

3. Place the main ON/OFF/WASH toggle switch to the

ON position, and wait until the float valve stops
adding water.

4. Adjust the water level to (1/4" to 3/8" (6.3 to 9.5 mm)

below the standpipe) the line in the water trough:

5. Loosen the two screws on the float valve bracket.

6. Raise or lower the float valve assembly as

necessary, then tighten the screws.

7. Move the main ON/OFF/ WASH toggle switch to the

OFF position. The water level in the trough will rise
above the standpipe and run down the drain.

8. Replace the siphon cap on the standpipe, and verify

water level and siphon action by repeating steps 3
through 5.

ICE BRIDGE THICKNESS CHECK

The ice thickness probe is factory-set to maintain the ice
bridge thickness at 1/8” (3.2 mm).

1. Inspect the bridge connecting the cubes. It should

be about 1/8” (3.2 mm) thick.

2. If adjustment is necessary, turn the ice thickness

probe adjustment screw clockwise to increase
bridge thickness, or counterclockwise to decrease
bridge thickness.

NOTE: Turning the adjustment 1/3 of a turn will change
the ice thickness about 1/16” (1.5 mm).

Ice Thickness Check

Make sure the ice thickness probe wire and the bracket
do not restrict movement of the probe.

SIPHON CAP

SET THE WATER LEVEL

TO THE LINE IN THE

WATER TROUGH

ADJUSTING SCREW

1/8” ICE BRIDGE THICKNESS