Before Calling for Service

Section 5

5-4

Part Number 000001130 12/08

Safety Limit #1

Freeze time exceeds 60 minutes for 3 consecutive freeze cycles.

Because there are many possible external problems,do not limit your diagnosis to only the items listed in
these charts.

Possible Cause

Check/Correct

Improper installation

See “Installation Instructions” Section 2 of this manual

Water system

Low water pressure (20 psi minimum.)

High water pressure (80 psi maximum.)

High water temperature (90°F/32.2°C maximum.)

Clogged water distribution tube

Dirty/defective water float valve

Loss of water from sump area

Defective water pump

Electrical system

Ice thickness probe out of adjustment

Harvest cycle not initiated electrically

Compressor relay not energizing

Compressor electrically non-operational

Restricted condenser air flow
(air-cooled models)

High inlet air temperature (110°F/43.3°C maximum.)

Condenser discharge air recirculation

Dirty condenser filter

Dirty condenser fins

Defective fan cycling control

Defective fan motor

Refrigeration system

Non-Manitowoc components

Improper refrigerant charge

Defective hot gas valve

Defective compressor

TXV starving or flooding (check insulation and bulb mounting)

Non-condensables in refrigeration system

Plugged or restricted high side refrigerant lines or component