OM-4428 Page 49

9-8. Overload Protection (Deutz F4L2011-Powered Units)

Ref. 803 657

2

1

9

8

7

4

!

Stop engine.

.

When a supplementary protector,
circuit breaker or fuse opens, it usu-

ally indicates a more serious prob-

lem exists. Contact Factory Autho-

rized Service Agent.

1

Fuse F1

2

Fuse F2

F1 and F2 protect the stator exciter

winding from overload. If F1 opens,

weld and generator power is low or

stops entirely. If F2 opens, weld output

is low or stops entirely. 4 kVA/kW gener-

ator power is still available.
3

Circuit Breaker CB4 (Not Shown)

4

Supplementary Protector CB5

(CC/CV Models Only)

5

Supplementary Protector CB6

(CC/CV Models Only)

6

Circuit Breaker CB10 (Not Shown)

7

Supplementary Protector CB11

8

Supplementary Protector CB12

9

Supplementary Protector CB13

10 Circuit Breaker CB14 (Not Shown)
CB4 protects the welding arc drive (dig)

circuit. If CB4 opens, electrode may

stick to the workpiece more frequently

during low voltage (short arc length)

conditions. CB4 automatically resets

when the fault is corrected.
CB5 protects the 24 volt ac output to re-

mote receptacle RC14, and 24 volt out-

put to field current regulator board PC1

(CC/CV models only). If CB5 opens,

weld output and 24 volt output to RC14

stops. On units with optional three-

phase generator, generator power out-

put at receptacle RC5 also stops if CB5

opens.
CB6 protects the 115 volt ac output to

remote receptacle RC14 (CC/CV mod-

els only). If CB6 opens, 115 volt output

to RC14 stops.
CB10 protects the engine battery cir-

cuit. If CB10 opens, the engine will not

crank. CB10 automatically resets when

the fault is corrected.
CB11 protects the weld control circuit.

On CC models, if CB11 opens the max

OCV circuit does not work and open cir-

cuit voltage is variable at all times (see

max OCV note under Weld Controls in

Section 6-2). If CB11 opens on CV mod-

els, weld output stops (generator power

is still available).
CB12 protects the field flashing circuit.

If CB12 opens, the generator may not

excite at start-up and weld and genera-

tor power output may not be available.
CB13 protects the engine control cir-

cuit. If CB13 opens, the engine does not

crank.
CB14 protects throttle solenoid TS1 on

units with auto idle option. If CB14

opens, the engine does not run at idle

speed. CB14 automatically resets when

the fault is corrected.
Press button to reset supplementary

protector.