OM-496 Page 39

Return To Table Of Contents

8-2.

Connecting To Optional Three-Phase Generator (CC/CV Models Only)

Ref. 197 399 / 802 332-E

.

Place Process/Contactor switch
in Electrode Hot - Stick position
when using three-phase genera-
tor (see Section 7-3
).

Single-Phase Generator Power

1

120/240 V 50 A Receptacle
RC5

RC5 is connected to the optional
three-phase generator and supplies
60 Hz single-phase power at weld/
power speed. Maximum output from
RC5 is 12 kVA/kW. Power available
at RC5 is reduced when welding.

2

Circuit Breaker CB7

Circuit breaker CB7 protects single-
phase receptacle RC5 and the load
wires from overload. If CB7 opens, all
generator output stops and the recep-
tacle does not work.

Three-Phase Generator Power

Y

Stop engine.

Y

Power and weld outputs are
live at the same time. Discon-
nect or insulate unused
cables.

.

Have qualified person install ac-
cording to circuit diagram and
Generator Power Guidelines
(see Section 12
).

Remove generator power panel
mounting screws. Tilt panel forward.

3

Lead 93

4

Lead 92

5

Lead 91

6

Lead 42 (Circuit Grounding
Lead)

7

Lead 90 (Neutral)

8

Isolated Neutral Terminal

9

Jumper Lead 42

10 Grounding Terminal

Jumper 42 is connected to lead 90 at
factory. Jumper 42 may be discon-
nected from neutral to meet applica-
ble electrical codes.

Lead 42 connects to front panel
Ground stud.

11 User-Supplied Leads

12 Circuit Breaker CB7 User

Terminals

Connect user-supplied leads to ter-
minals on CB7 and to the isolated
neutral terminal and grounding termi-
nal as necessary.

.

Circuit breaker CB7 protects
single-phase receptacle RC5
and the load wires from overload.
If CB7 opens, all generator out-
put stops and the receptacle
does not work.

Reinstall generator power panel.

Tools Needed:

Volts

Amps

KVA/KW

Single

120/240

50

12

Three

240

36

15

60 Hz

Frequency

Engine Speed

1850 RPM

AC

Phase

1

Phase

3

Output

Lead 42 connects to GROUND stud on
front of unit.

Jumper 42 is connected to 90 at factory.

1

2

91

92

93

240V

120V

120V

240V

240V

1-Phase

3-Phase

3

4

5

6

7

8

9

10

11

12

Rear Of Panel

Three-Phase Power Connection

2

Single-Phase Power Connection

92

90

91

93

Y

Close panel opening
if no connections are
made to generator.

Y

Close panel
opening if no
connections
are made to
generator.

240V

Remove plug
before inserting
leads. Reinstall
bushing.