3-17. Selection A Location And Connecting 1-Phase Input Power

Ref. 803 543-E / 803 766-A

Tools Needed:

3

2

7

6

4

!

Installation must meet all National and

Local Codes - have only qualified

persons make this installation.

!

Disconnect and lockout/tagout input

power before connecting input

conductors form unit.

!

Always connect green or green/yellow

conductor to supply grounding terminal

first, and never to a line terminal.

!

Warning: This unit is either a

200/230/460 ac input voltage model or

460/575 ac input voltage model. See

rating label on unit and check voltage

available at site to be sure it matches

the voltage specified on the rating

label.

Three Conductor Power Cord Preparation
1

Input Power Cord Strain Relief

2

Input Power Cord

3

Black And White Input Conductors (L1

And L2)

4

Red Input Conductor

5

Green Or Green/Yellow Grounding

Conductor

6

Insulation Sleeving

7

Electrical Tape

Insulate and isolate red conductor as shown.
Disconnect Device Input Power

Connections
8

Disconnect Device (switch shown in

the OFF position)

9

Disconnect Device Grounding Terminal

10 Disconnect Device Line Terminals

Connect green or green/yellow grounding

conductor (see Item 5) to disconnect device

grounding terminal first.

Connect input conductors L1 and L2 to

disconnect device line terminals.

11 Over-Current Protection

Select type and size of over-current protec-

tion using Section 3-13 (fused disconnect

switch shown).

Close and secure door on disconnect device.

Remove lockout/tagout device, and place

switch in the On position.

5

Rear Panel

18 in. (457 mm)

for airflow

!

Do not move or operate

unit where it could tip.

=GND/PE Earth Ground

8

1

5

3

9

10

11

L1

L2

2

1