8-4. Generator Power Receptacles (CE Models)

.

Generator power is not affected by weld
output.

1

130 V 32 A AC Receptacle RC1

2

220 Volt 16 A AC Receptacle RC2

3

130 Volt 16 A AC Receptacle RC3

Receptacles supply 60 Hz single-phase

power at weld/power speed.
4

Circuit Breaker CB1

5

Circuit Breakers CB2 And CB3

CB1 protects RC1 and the generator wind-

ing from overload. If CB1 opens, RC1 and

RC2 do not work. Place switch in On position

to reset breaker.

CB2 protects RC2, and CB3 protects RC3

from overload. If a circuit breaker opens, the

receptacle does not work. Place switch in On

position to reset breaker.

.

If a circuit breaker continues to open,
contact Factory Authorized Service
Agent.

Maximum output is 4 kVA/kW from RC1 and

2.2 kVA/kW from RC2 or RC3. Maximum

output from all receptacles is 4 kVA/kW.
Combined output of receptacles is limited to

4 kVA/kW output of generator. If maximum

output is exceeded, auxiliary equipment will

stop or not run properly.
EXAMPLE: If 20 A is drawn from RC1, only

8 A is available at each of the other

receptacles.
(110 V x 20 A) + ( 110 V x 8 A) + (110 V x 8

A) = 4 kVA/kW.

Ref. 204 258

1

4

2

3

5