Intelligent Motion Systems MDriveAC User Manual

Page 44

Advertising
background image

2-17

Part 2: Interfacing and Configuring

Screen 2: I/O Settings Configuration Screen

The I/O Settings screen may be accessed by clicking View > IO Settings on the menu bar. This screen is used to
configure the Input Clock type, the filtering and the Active High/Low State of the Enable Input.

Input Clock Type

The Input Clock Type translates the specified pulse source that the motor will use as a reference for establishing
stepping resolution based on the frequency.

The three clock types supported are:

1. Step/Direction
2. Quadrature
3. Up/Down

The Clock types are covered in detail in Section 2.2: Logic Interface and Connection.

Input Clock Filter

The clock inputs may also be filtered using the Clock IOF pull down of the IMS SPI Motor Interface. The filter
range is from 50 nS (10 MHz) to 12.9 µSec. (38.8 kHz). Table 2.4.3 shows the filter settings.

Input Clock Filter Settings

Min Pulse

Cutoff Frequency

50 nS

10 MHz

150 nS

3.3 MHz

200 nS

2.5 MHz

300 nS

1.67 MHz

500 nS

1.0 MHz

900 nS

555 kHz

1.7 µS

294.1 kHz

3.3 µS

151 kHz

6.5 µS

76.9 kHz

12.9 µS

38.8 kHz

Table 2.3.4: Input Clock Filter Settings

Enable Active High/Low

The parameter sets the Enable Input to be Active when High (Default, Disconnected) or Active when Low.

Warning Temperature

The Warning Temperature parameter allows you to set a pending over-temperature threshold for the MDriveAC
Plus Microstepping. When that threshold is reached, a "TW" error code will appear in the Fault field. The Fault
output will also begin to activate/deactivate at 1 second intervals (1/2 second on, 1/2 second off).

Input Clock Type

(Step/Dir, Quadrature or

Up/Down)

Input Clock Filter

Active High/Low

State of the

Enable Input

Warning

Temperature

Figure 2.3.8: SPI Motor Interface I/O Settings Screen