1-4 Connecting the Alarm I/O Terminals

Connect the alarm I/O terminals with external equipment such as a sensor, buzzer,
etc.

Input Requirements

• No-voltage relay “A-contact” input or NPN open

collector input
(A-contact: Contact is normally open and closes
when the alarm is turned on.)

• Active low level
• Latch/Momentary (at least 500 ms)
• Circuit current at low level: 0.6 mA
• Voltage applied at high level: 3.3 V

Alarm Input Terminal

This terminal is for connecting with a sensor, infrared, door or metallic, or a manual
switch.

CLASS 2 ONL

Y F

or USA

ISOLA

TED PO

WER ONL

Y

POWER

G

2

2

1

1

OUT COM

ALARM

DC12V

A

C24V

OUTPUT

INPUT

PUSH

For EUR

OPE

10BASE-T/100BASE-TX

For USA

DO NOT CONNECT TO THE
TELEPHONE NETWORK

Push

VN-C10

Sensor

Connection

Example 1

Terminal 1 or 2

OUT

R

DC3.3V

(Alarm input equivalent circuit)

Grounding
terminal

GND

0.6mA

R

VCC

Sensor

Connection

Example 2

OUT

GND

3.3V

Relay, switch etc.

Press the buttons for connecting or disconnect-
ing cables as shown on the left.

Cable Specifications
50 m max.

UL1007, UL1015 or equivalent

AWG #22 to AWG #18 or equivalent

Caution

Due to external noise, the camera may not
work properly even if the length of the cable
is less than 50 m. If this occurs, use a
shielded cable or keep the cable away from
the noise source.