Sierra Monitor Corporation 5100-06-IT User Manual

Page 24

Advertising
background image

Model 5100-XX-IT Toxic Gas Sensor Module

Page: 20

5.4 SET-UP

The sensor module set-points menu is used to initially set-up the alarm set points, relay actions, gas type and
range, 4-20 mA action or RS-485/Sentry address and baud rates, Digital Input and Warm-up time. Use the [▲]
or [▼] keys to select following menus and press [E] to select.

Alarms: Use the [▲] or [▼] keys to select Low Alarm (Warning) or High Alarm (Alarm) menu. Key

[▲] will adjust the setpoint upwards and Key [▼] will adjust the value downwards. Once it reaches
the desired setpoint, Key [E] will accept it and ACK will appear.

Set-points can be configured using this menu up to the following values:

NOTE:

To enable rising O2 Alarm set warning setpoint higher than 20.9%

Relays: Use the [▲] or [▼] keys to select High Alarm (Alarm) or Low Alarm (Warning) relay menu

and press [E]. Use the [▲] or [▼] keys to select the correct alarm relay action for the application,
Latch, Sentry or Non-Latch. Selecting “Sentry” enables the Sentry controller to make all alarm
action decisions. * indicates the current selection.

Range: Use the [▲] or [▼] keys to select Range menu and press [E]. When “Range” is selected

menu provides any choices of ranges available for the gas type selected. Use the [▲] or [▼] keys
to select the desired range. If the “User” range is selected, use the [▲] or [▼] keys to adjust the
high end of the range desired.

Factory Range Set-up

Model Range

Other

Available

5100-03-IT 5-25% 0-25%
5100-04-IT

0-500

PPM

Variable

5100-05-IT

0-100

PPM

Variable

5100-06-IT

0-10

PPM

None

5100-08-IT 0-3

PPM None

5100-10-IT

0-100

PPM

Variable

5100-12-IT

0-20

PPM

None

5100-21-IT 0-20

PPM None

5100-25-IT 0-100

PPM

Variable

5100-26-IT 0-10

PPM None

5100-88-IT 0-5000

PPM

Variable

4-20mA: Use the [▲] or [▼] keys to select Calib or CalibOut menu and press [E]. The “Calib”

section of the menu allows the user to calibrate the 4 mA and 20 mA outputs. To calibrate the 4 mA
and 20 mA outputs it is necessary to have an amp meter connected to the 5100-XX-IT and upon
selecting the 4 mA output calibration then the [▲] or [▼] keys can be used to adjust the 4 mA
reading on the amp meter until it reads 4 mA. Similar steps can then be performed for the 20 mA
output. The CalibOut section allows the user to select the 4-20 mA output action desired during
calibration. * indicates the current selected value. Available selections include:

Factory Alarm Set Points

Model Warning

Alarm

5100-03-IT 19.5%

16.5%

5100-04-IT

50 PPM

100 PPM

5100-05-IT

10 PPM

20 PPM

5100-06-IT

2.0 PPM

5.0 PPM

5100-08-IT

0.3 PPM

1.0 PPM

5100-10-IT

10 PPM

20 PPM

5100-12-IT

2 PPM

4 PPM

5100-21-IT

5 PPM

10 PPM

5100-25-IT

25 PPM

50 PPM

5100-26-IT 2.0

PPM 5.0

PPM

5100-88-IT

1000 PPM

2500 PPM

Advertising