Sierra Monitor Corporation 5100-06-IT User Manual

Page 32

Advertising
background image

Model 5100-XX-IT Toxic Gas Sensor Module

Page: 28

7.3 TRANSMITTER REPLACEMENT

The transmitter assembly should be replaced when it is determined that it is unreliable, noisy or cannot be
adjusted for calibration. This may occur due to age, corrosion or failed components.

To replace the transmitter assembly:

a. Remove the cover of the main enclosure.
b. Unscrew the two thumb screws in the top of the cover plate, lift the assembly and rotate 90

o

to relieve the

wiring service loop.

c. Remove all wires from bond, marking them carefully so they can be correctly replaced.
d. Unplug the sensor connector from the transmitter.
e. Reverse the preceding steps to install the new transmitter.
f. Restore power and allow a minimum of 30 minutes for stabilization before re-calibration.

7.4 SENSOR REPLACEMENT

NOTE: Refer to Appendix H for information on sensor electrolyte replacement for 5100-25-IT and 5100-26-IT.

The gas sensor which is located inside the sensor assembly housing can be replaced without replacement of
the housing. The gas sensor needs replacement when:

The “CAL-FAIL” message appears after calibration.

The sensor output signal is noisy, causing erroneous gas level readings.

The “Sensor Failure” message displays.

To replace the sensor:

a. Confirm that system power has been removed.
b. Remove the gas sensor module enclosure cover.
c. Unscrew the two thumb screws in the top of the faceplate, lift the transmitter assembly and rotate 90

o

to

relieve the wiring service loop.

d. Unplug the sensor connector from the transmitter.
e. Unscrew the old sensor assembly from the enclosure conduit hub. Remove the sensor assembly with its

harness.

f. Unscrew sensor housing cover from the sensor.
g. Carefully pull the old sensor straight up from the socket.
h. Press the new sensor into the socket.
i. Reverse the preceding steps to install the sensor assembly.
j. Allow the new sensor to stabilize for a minimum of 60 minutes and then calibrate using the procedure in

Section 6.

7.5 INSTALLATION INSPECTION

Prior to system start-up or trouble shooting, the entire system should be visually inspected. The following are
guidelines for that inspection:

7.5.1 CONTROLLER

INSTALLATION

• Controller installed in conformance to instruction manual recommendations.

• AC power is correctly grounded.

• Hot AC and relay connections have safety covers installed.

7.5.2 CABLING

INSTALLATION

• All splices are soldered or via terminal block.

• Cabling is away from sources of electrical noise or RFI where possible.

7.5.3 SENSOR MODULE INSTALLATION

• Module installation in conformance with this manual.

• Modules accessible for calibration.

• Wiring terminations clean and correct.

Advertising
This manual is related to the following products: