Model 5100-XX-IT Toxic Gas Sensor Module

Page: 21

Track – the 4-20mA value tracks the calibration gas exposed to the gas sensor module

C2.50mA – the 4-20mA value is held at 2.50mA during calibration

C4.00mA – the 4-20mA value is held at 4.0mA during calibration.

RS-485 - Use the [▲] or [▼] keys to select Address or Baud rate menu and press [E]. Note that the

5100-XX-IT has a rotary switch on the faceplate and it is used to select addresses 1-15. When
connected to Sentry the user can select 1-8 and when using Modbus RS-485 the user can select
addresses 1-15. For Modbus addresses above 15, set the rotary switch to 0 and then use the
“Address” menu to select any address between 16 and 254. The Baud rate menu allows the user
to select a baud rate of 38400, 19200, 9600, 4800 or 2400. * indicates current selection. (Sentry
default is 9600)

DigInput – Use the [▲] or [▼] keys to select supervised or Non-supervised digital input and then

press [E] to change.

Function

Display

Description

Reference

M

E

 

M

E

 

M

E

 

M

E

 

M E

M E

M E

M E

M

E

 

M

E

 

Use  or  keys to adjust to new set point

M E

M

E

 

M

E

 

M E

M

E

 

M E

M E

Down

*Sentry

Low Alarm Relay set to Sentry

Down

Sentry

NOTE: Sentry indicates that Sentry controls relay
action and not the IT Sensor Module

Enter

Latch

Use  or  keys to adjust to new relay action
(Latch, Sentry, NonLatc) * indicates current

Down

L.Relay

S.P. Function - Low Alarm Relay Adjust

Relays Set Point Adjustment Example

Enter

H. Relay

S.P. Function - High Alarm Relay Adjust

*B

H.Alarm

S.P. Function - High Alarm Adjust

Enter

ACK

Momentary Acknowledge of new Set Point

Down (x5) HASP:55-

High Alarm Set Point: new = 55

Enter

HASP:60-

High Alarm Set Point: current = 60

High Alarm Set Point Adjustment Example

Enter

H.Alarm

S.P. Function - High Alarm Adjust

*A

Down

Dig Input

S.P. Function - RS-485/Sentry Output Adjust

* E Below

Down

4-20mA

S.P. Function - 4-20 mA Adjust

* D Below

Down

Relays

S.P. Function - Range Adjust

* C Below

Down

Relays

S.P. Function - Relays Adjust

* B Below

Enter

Alarms

S.P. Function - Alarm Adjust

* A Below

Mode

SETUP:---

Mode Function - Set Point Adjustments

Mode

ALMRSET:

Mode Function - Alarm Reset

Key

--0%LEL-

Default Display

Mode

CALIB:--

Mode Function - Calibrate

Table 5 - 3: Set-Up Configuration