Marley, Engineering data: freeze prevention, Fluid cooler – SPX Cooling Technologies Marley MC 7014H081 - 7014K121 User Manual

Page 14

Advertising
background image

Marley

/

MC

Fluid Cooler

/

Engineering Data: Freeze Prevention

14

Fluid Cooler Coil

When the ambient temperature falls below 0°C,

heat loss from the coil can be substantial even without

recirculating water flowing over the coil. The process

fluid, without an applied heat load, may be prone to

freezing. There are various methods to protect against

coil freezing.

Ethylene and propylene glycol solutions are the

best means to protect against coil freezing and are

recommended for most installations. The appropriate

concentration of ethylene or propylene glycol should be

determined based on the required protection from low

ambient temperatures.

If the use of an industrial antifreeze solution is not

compatible with the system, another accepted method

of preventing coil freezing is to maintain a sufficient flow

rate and heat load on the process fluid. The fluid exiting

the coil must be maintained at or above 7°C at the full

process flow rate. If the process load does not yield such

a heat load, it may be necessary to apply a supplementary

heat load to the process fluid.

Draining the coil is not considered to be an acceptable

means of protection against freezing. Introducing air to

the interior of the bundle will promote corrosion of the

heat exchanger coil. In an emergency, this alternative can

be used in the event that the process fluid drops below

7°C, the ambient temperature is below freezing and the

coils are not protected with industrial antifreeze.

Cycling of the recirculating water pumps should not be

used to control process flow temperatures. Coils may be

used for seasonal dry operation followed by seasonal wet

operation, but not for frequent cycling of the recirculating

water pump. Such operation may lead to an excessive

scale buildup resulting in a decrease in efficiency.

Fluid Cooling Recirculating Water

When the ambient air temperature falls below 0°C,

the recirculating water within the fluid cooler can freeze.

Marley Technical Report #H-003 “Operating Cooling

Towers in Freezing Weather” describes how to

prevent freezing during operation. Ask your Marley sales

representative for a copy or download a copy at

spxcooling.com.

During shutdown, water collects in the basin and may

freeze solid. You can prevent freezing by adding heat to

the water left in the basin—or, you can drain the fluid

cooler and all exposed pipework at shutdown.
Electric Basin Heaters

An automatic basin water heater system, consisting of

the following components:

CAUTION

Freezing ambient conditions could cause significant
damage to the heat exchanger coil of the MC Fluid
Cooler. To avoid possible damage, it is imperative to
provide for adequate freeze protection.

• Standard weatherproof (IP55) enclosure, rating

depending on model and minimum expected winter

temperature (see table below):

• Ratings are in kW for specified ambient temperature.

For lower ambient temperatures refer to SPX

engineering for advice.

• Standard electircal supply is 380/415 V 3ph (220/240V 1

ph available as extra cost option).

• Heater has an integral thermostat, set point nominally

3°C but adjustable to suit operating requirements.

The basin heater option is only for freeze protection

of the recirculation water in collection basin. The

basin heater option does not protect the coil during

freezing weather.

Heater components are normally shipped separately

for installation by others.

Indoor Storage Tank

With this type of system, water flows from an indoor

tank and back to the fluid cooler where it is cooled

and recirculated. The water flows by gravity from the

fluid cooler to the tank located in a heated space. At

shutdown, all exposed water drains into the tank where it

is safe from freezing.

The amount of water needed to successfully operate

the system depends on the fluid cooler size and m

3

/hr

and on the volume of water contained in the piping

system to and from the fluid cooler. You must select a

tank large enough to contain those combined volumes—

plus a level sufficient to maintain a flooded suction on

your pump. Control makeup water according to the level

where the tank stabilizes during operation.

Advertising
This manual is related to the following products: