Marley, Specifications: options, Fluid cooler – SPX Cooling Technologies Marley MC 7014H081 - 7014K121 User Manual

Page 23

Advertising
background image

Specifications

Specification Value

Marley

/

MC

Fluid Cooler

/

Specifications: Options

23

temperature at the coil and the other

for set point. Process temperature input

shall be obtained using a thermal sens-

ing device on the process coil and wired

back to the solid state temperature

controller in the control panel. Staging

of multiple motors and speeds will be

accomplished with an integral PLC.

Vibration Limit Switch:

6.5

Add the following paragraph in the

Mechanical Equipment section: A

single-pole, double-throw vibration

limit switch in a IP55 housing shall be

installed on the mechanical equipment

support for wiring into the owner’s

control panel. The purpose of this

switch will be to interrupt power to the

motor in the event of excessive vibra-

tion. It shall be adjustable for sensitiv-

ity, and shall require manual reset.

Basin Heater:

11.2 Add the following paragraph in the

Cold Water Basin section: Provide

an electric immersion heater for each

cell of the fluid cooler to prevent freez-

ing of water in the collection basin

during periods of shutdown. The rod

type heater is installed in the side of

the cold water basin. Each heater will

include an integral thermostat, set

point nominally 4°C but adjustable to

suit local operating requirements.

Fan Motor Variable Speed Drive:

Marley All Weather ACH550 System

6.4 Add the following paragraph in the

Mechanical Equipment section when

VFD is used with customers Building

Management System: A complete UL

listed Variable Speed Drive system in a

IP10 indoor, IP52 indoor or IP14 outdoor

enclosure shall be provided. The VFD

shall use PWM technology with IGBT

switching and integrated bypass design.

VFD out put switching shall not cause

mechanical issues with gearbox teeth

or drive shafts. The VFD shall catch a fan

spinning in the reverse direction without

tripping. The panel shall include a main

disconnect with short circuit protection

and external operating handle, lockable

Unless specified otherwise, a Fire

Fighting Enterprises switch will be provid-

ed. A double-pole, double-throw model

is also available. The requirement for

manual reset assures that the fluid cooler

will be visited to determine the cause of

excess vibration.

The Marley basin heater components described at left represent our

recommendation for a reliable automatic system for the prevention of

basin freezing. They are normally shipped separately for installation at

the jobsite by the installing contractor. When purchased in conjunction

with the enhanced Control System option, however, they are customar-

ily factory-mounted and tested.

Submerged in basin water, in which zinc ions are present, copper

immersion heaters must not be used. Insist upon stainless steel.

The ambient air temperature that you insert in the specifications

should be the lowest 1% level of winter temperature prevalent at site.

Marley VFD drive systems are designed to combine absolute tem-

perature control with ideal energy management. The fluid cooler user

selects a cold water temperature and the drive system will vary the

fan speed to maintain that temperature. Precise temperature control

is accomplished with far less stress to the mechanical equipment

components. The improved energy management provides fast pay-

back.