Specifications

Specification Value

Marley

/

MC

Fluid Cooler

/

Specifications: Base

19

8.0

Drift Eliminators:

8.1

Drift eliminators shall be PVC, triple

pass and shall limit drift losses to no

more than 0.005% of the design water

flow rate.

9.0

Hot Water Distribution System:

9.1

A pressured spray system shall distrib-

ute water evenly over the fill. Header

box shall be steel and branch arms

shall be PVC with polypropylene spray

nozzles attached to the branch arms by

an integral screw connection for ease

of removal and cleaning. The spray

system shall provide full coverage

of the coil at a flow rate sufficient to

ensure complete wetting of the coil at

all times.

10.0 Casing:

10.1 The casing shall be heavy gauge G-600

galvanized steel and shall be capable

of withstanding the loads described in

paragraph 5.1.

11.0 Access:

11.1 A large galvanized, rectangular access

door shall be located on both end

panels for entry into the cold water

basin. Rectangular panels are shall be

provided for access to the fan plenum

area to facilitate inspection and allow

maintenance to the fan drive system

12.0 Cold Water Collection Basin:

12.1 The collection basin shall be heavy-

gauge galvanized steel and shall

include the number and type of suction

connections required to accommodate

the out-flow piping system shown on

the plans. Suction connections shall be

equipped with debris screens. A fac-

tory installed, float operated, mechani-

cal make-up valve shall be included. An

overflow and drain connection shall be

provided in each cell of the fluid cooler.

The basin floor shall slope toward the

drain to allow complete flush out of

debris and silt which may accumulate.

13.0 Warranty:

13.1 The MC Fluid Cooler shall be free from

defects in materials and workmanship

for a period of eighteen (18) months

from the date of shipment.

Drift rate varies with design water loading and air rate, as well as drift

eliminator depth and number of directional changes. The indicated

rate of 0.005% is easily achievable without premium cost. If a lower

rate is required, please discuss with your Marley sales representative.

The combination of PVC piping and polypropylene nozzles is very

resistant to the build-up of scale and slime.

The MC fluid cooler design offers side-suction as standard. Bottom

outlets may be supplied to accommodate a variety of piping schemes.

Unless so specified, the fluid cooler you may be asked to approve

may only be available with one type of suction connection requiring

you to redesign your piping layout.

The sloping floor and low-level drain is valuable because it provides a

way to achieve flush-out cleanability.