Specifications

Specification Value

Marley

/

MC

Fluid Cooler

/

Specifications: Options

24

in the off position for safety. The VFD

system shall receive a speed reference

signal from the Building Management

System monitoring the tower fluid tem-

perature. As an option to receiving the

speed reference signal from a building

management system, the drive must

have the capability to receive a 4-20 ma

temperature signal from an RTD trans-

mitter. The VFD shall have an internal PI

regulator to modulate fan speed main-

taining set point temperature. The drive's

panel display shall be able to display

the set-point temperature and cold-fluid

temperature on two separate lines. The

bypass shall include a complete mag-

netic bypass circuit and with capability

to isolate the VFD when in the bypass

mode. Transfer to the bypass mode shall

be manual in the event of VFD failure.

Once the motor is transferred to the by-

pass circuit the fan motor will run at con-

stant full speed. The bypass circuit will

not modulate ON and OFF based on fluid

temperature. The application must be

able to handle very cold fluid tempera-

tures while the VFD is in a by-pass mode.

Operator controls shall be mounted on

the front of the enclosure and shall con-

sist of start and stop control, bypass/VFD

selection, Auto/Manual selections, manu-

al speed control. To prevent heating prob-

lems in the fluid cooloer fan motor and

to assure proper gear reducer lubrication

the VFD system shall de energize the

motor once 25% motor speed is reached

and cooling is no longer required. The

fluid cooler manufacturer shall supply

VFD start-up assistance. Tower vibration

testing throughout the speed range is

required to identify and lockout any natu-

ral frequency vibration levels which may

exceed CTI guidelines.

Marley Premium VFD System

6.4 Add the following paragraph in the

Mechanical Equipment section when

VFD is used as a stand alone system:

A complete UL listed Variable Speed

Drive system in a IP52 indoor or IP14

outdoor enclosure shall be provided. The

VFD shall use PWM technology with

IGBT switching and integrated bypass

design. VFD output switching shall not

cause mechanical issues with gearbox