Where a fluid cooler is installed in a building well or there are high

surrounding walls, it is possible that a proportion of the hot and

humid discharge air will be drawn back into the fans thus increasing

the inlet wet bulb temperature with detriment to the fluid cooler per-

formance.

The tapered discharge duct is intended to increase the exit velocity

by up to 70% in order to reduce the effects of recirculation in some

installations. Experience and sound judgement should be exercised to

determine when and if a duct is required.

If the surrounding walls are much higher than the fluid cooler dis-

charge height, then extensions to the tapered duct may be installed.

Discharge Hood:

6.4 Add the following paragraph

to the Mechanical Equipment

Section: There shall be a galva-

nized steel tapered duct on the

discharge side of the fluid cooler.

Drift eliminators shall be reposi-

tioned into the lower section of

the duct.