Specifications: Options

21

Convenience and Safety Options

Top Access Platform:

11.2 Add the following paragraph in

the Access section: There shall be

an access platform at the top of the

fluid cooler to allow access to the drift

eliminators and distribution system.

The platform shall be free-standing

galvanized steel bar grating, sup-

ported by galvanized steel framework.

The platform shall be surrounded by

a handrail, kneerail, and toeboard

designed according to meet local

safety requirements. Handrails and

kneerails shall consist of 42mm O.D. x

15 gauge galvanized structural tubing,

the handrail of which shall be capable

of withstanding a 890 N concentrated

live load in any direction. Posts are

51mm x 51mm square structural tub-

ing and shall be spaced on centers of

2.44m or less. A ladder shall be per-

manently attached to the platform and

to the casing of the fluid cooler, rising

from the base of the fluid cooler to the

top of the handrail.

Ladder Extension:

11.2 Add the following to the end of

paragraph 11.2: Provide a ladder

extension for connection to the foot

of the ladder. This extension shall

be long enough to rise from the roof

(grade) level to the base of the fluid

cooler. The installing contractor shall

be responsible for cutting the ladder to

length; attaching it to the foot of the

fluid cooler ladder; and anchoring it at

its base.

Ladder Safety Cage:

11.3 Add the following paragraph in the

Access section: A heavy gauge galva-

nized steel safety cage shall surround

the ladder, extending from a point

approximately 2150mm above the foot

of the ladder to the top of the handrail.

Periodic inspection and maintenance of a fluid cooler distribution

system is fundamental to preserving maximum cooling system effi-

ciency. All fluid coolers—crossflow or counterflow—are subject to

clogging to varying degrees by waterborne contaminants such as

pipe scale and sediment. Therefore, safe and easy access to these

components is of significant value to the operator.

Access can be provided in a number of ways, including portable

ladders or scaffolding, but for maximum safety and convenience, a

field installed Marley access platform with guardrails is available to

make this task as safe and user-friendly as possible. Further, its loca-

tion on the side of the fluid cooler does not add to the height of the

unit, preserving architectural integrity. It also saves the owner time

and money, in that maintenance personnel may devote their time to

inspection rather than searching for ladders or erection of portable

scaffolding.

Many fluid coolers are installed such that the base of the unit is

600mm or more above the roof or grade level. This makes it difficult

to get up to the foot of the attached ladder. The ladder extension alle-

viates this problem. Marley ladder extensions are available in stan-

dard 1524mm and 3353mm lengths.