Specifications

Specification Value

Marley

/

MC

Fluid Cooler

/

Specifications: Options

22

Access Door Platform:

11.4 Add the following paragraph in the

Access section: There shall be an

access platform at the base of the fluid

cooler extending across the width of

the casing. The platform shall be gal-

vanized steel bar grating, supported by

galvanized steel framework attached to

the fluid cooler. The platform shall be

surrounded by a handrail, kneerail, and

toeboard.

Distribution System Access Door

Platform:

10.5 Add the following paragraph in the

Access section: There shall be an

access platform at the level of the

distribution system access door. The

platform shall be galvanized steel bar

grating, supported by free-standinggal-

vanized steel framework attached to

the fluid cooler. The platform shall be

surrounded by a handrail, kneerail, and

toeboard.

Control Options

Control System:

6.4 Add the following paragraph in the

Mechanical Equipment section: The

fluid cooler shall be equipped with a

UL 508 control system in a IP14 or

IP56 outdoor enclosure capable of

controlling single-speed or two-speed

motors as required, and designed

specifically for fluid cooler applications.

The panel shall include a main fused

disconnect with an external operating

handle, lockable in the off position for

safety. Across-the-line magnetic start-

ers as required shall be controlled with

a solid state temperature controller.

Door mounted selector switches shall

be provided to enable automatic or

manual control and wired for 120VAC

control. Control circuit to be wired out

to terminal blocks for field connection to

remote vibration switches. The tempera-

ture controller shall be adjustable for

the required process temperature. The

temperature controller will display two

temperatures, one for process

Where fluid coolers are installed on an elevated grillage or piers, it is

often difficult to get to—and through—the access door conveniently.

This platform provides easy, safe and comfortable access to that door.

This platform provides easy, safe and comfortable access to the

access door facilitating inspection of the fill, distribution nozzles and

the underside of the drift eliminators.

If it is your opinion that the control system for the fluid cooler be part

of the fluid cooler manufacturer’s responsibility, we are in whole-

hearted agreement with you. Who better to determine the most effi-

cient mode and manner of a fluid cooler’s operation—and to apply a

system most compatible with it—than the designer and manufacturer

of the fluid cooler?

Marley variable speed drives are

also available for the ultimate

in temperature control, energy

management and mechanical

equipment longevity.