background image

Specifications

Specification Value

Marley

/

MC

Fluid Cooler

/

Specifications: Base

18

take the above water quality and load

carrying capabilities into account in the

selection of their materials of manufac-

ture.

7.0

Mechanical Equipment:

7.1

Fan(s) shall be forward curved cen-

trifugal-type, which are statically and

dynamically balanced. The fan impeller

is manufactured from galvanized steel,

blades are riveted to the center plate

and inlet rings and have stay rods to

ensure maximum concentricity and

rigidity. The stay rods are adjusted by

the manufacturer during the balancing

operation and require no field adjust-

ment. Fan(s) shall be driven through

one-piece, multi-groove, V-belt, pulleys,

and spherical roller bearings. Bearings

shall be rated at an L

10

life of 50,000

hours, or greater. A hinged motor

adjustment plate with threaded ten-

sioning bolts shall be installed to allow

correct belt tensioning.

7.2

Motor(s) shall be ____ kW maximum,

Totally Enclosed, 1.15 service fac-

tor, variable torque, and specially

insulated for fluid cooler duty. Speed

and electrical characteristics shall be

______ RPM, single-winding, 3 phase,

50 hertz, ____ volts. Motor shall oper-

ate in the shaft-horizontal position and

nameplate kW shall not be exceeded

at design operation

7.3

The complete mechanical equipment

assembly for each cell shall be sup-

ported by a rigid, galvanized steel

structural support that resists misalign-

ment between the motor and sheaves.

The mechanical equipment assembly

shall be warranted against any failure

caused by defects in materials and

workmanship for no less than five (5)

years following the date of fluid cooler

shipment. This warranty is limited to

the fan, fan shaft, bearings, sheaves

and mechanical equipment support.

The motor, motor components and

belt(s) are warranted by their manufac-

turer.

The Marley drive system features all-aluminum sheaves (pulleys),

power band belts, and long-life bearings for dependable service.

To reduce cost, some manufacturers may use TEAO motors, whose

only source of cooling is the flow of air produced by the fluid cooler

fan. They are sometimes applied at kWs significantly beyond their

nameplate rating.

Unless otherwise specified, motor speed will be 1500 RPM, 50 Hertz

on standard models. If you prefer the operating flexibility of two-

speed operation, please specify two-speed, single-winding motors

which offer full and half speeds for maximum energy savings.

Incidentally, two speed motors are a far better choice than separate

“pony” motors which simply double the problems indicated above.

The value of a 5 year mechanical equipment warranty speaks for

itself.