Marley, Specifications: options, Fluid cooler – SPX Cooling Technologies Marley MC 7014H081 - 7014K121 User Manual

Page 25

Advertising
background image

Specifications

Specification Value

Marley

/

MC

Fluid Cooler

/

Specifications: Options

25

teeth or drive shafts. The VFD shall catch

a fan spinning in the reverse direction

without tripping. The panel shall include

a main disconnect with short circuit pro-

tection and external operating handle,

lockable in the off position for safety.

The system shall include a solid state,

PI temperature controller to adjust fre-

quency output of the drive in response

to the tower fluid temperature. The

temperature of the fluid and set point

shall be displayed on the door of the

control panel. The bypass shall include a

complete magnetic bypass circuit with

capability to isolate the VFD when in

the bypass mode. Transfer to the bypass

mode shall be automatic in the event of

VFD failure or for specific trip conditions

allowing safe transfer of utility voltage

to the motor. Automatic bypass with an

earth ground condition is not allowed.

The bypass contactor shall be cycled

on and off while operating in bypass, to

maintain the set-point temperature of

the fluid. The drive design shall be oper-

ated as a stand-alone system without

the need for a BMS system. Operator

controls shall be mounted on the front of

the enclosure and shall consist of start

and stop control, bypass/VFD selector

switch, Auto/Manual selector switch,

manual speed control, and solid-state

temperature controller. An emergency

bypass selector switch internal to the

panel allowing the fluid cooler fan motor

to be run at full speed shall be furnished.

To prevent heating problems in the fluid

cooler fan motor and to assure proper

gear box lubrication the VFD system

shall de energize the motor once 25%

motor speed is reached and cooling is

no longer required. The VFD shall include

de-icing logic with auto canceling and

adjustable time. Speed in De-Ice mode

shall not exceed 50% motor speed. The

fluid cooler manufacturer shall supply

VFD start-up assistance. Tower vibration

testing throughout the speed range is

required to identify and lockout any natu-

ral frequency vibration levels which may

exceed CTI guidelines.