Ancb/dn specifications, Communication comparisons – Siemens ADVANCE NETWORK COMMUNICATIONS BOARD/DATANET 2000592-001 User Manual

Page 13

Advertising
background image

ANCB/DN Specifications

Protocol and Addressing

Open Systems standard TCP/IP protocol and addressing
(Transmission Control Protocol/Internet Protocol); Full Class A, B and
C addresses and subnet masking supported

Wiring Connections

• Two part connectors with screw-terminals provided for cable

connection

• Fiber Optic Coupler for Fiber Optic Connections

DataNET Option, Standard
Cable

• Cable connection by Belden 9182 (single pair) or Belden

SSD1743 (two pairs) or equivalent; two pairs of wires are
required to support redundancy

• Two pairs of cable is required to support redundancy

• Shielded cable or unshielded cable in conduit is required for

conformance to CE certified installation

• Two part connectors with screw-terminals provided for field

connection

DataNET Option, Fiber Optic
Cable

• Fiber optics connection by 62.5 multi-mode cable corresponding

to 10BaseFL Ethernet specification

• Two pairs of fibers are required to support redundancy

• Type ST mating connectors provided for field connection

• Approximately 3 mbps base transmission rate; uses dedicated

transmission technique that does not require collision detection to
achieve high data throughput efficiency

• Maximum Length 5000 feet ( 1.7km)

Fiber Optic Coupler

• Two (Tx, Rx) ST-Style Connectors (Amp type 2.5mm Bayonet)

Serial Port

• Standard RS-232 port for attachment of a laptop computer, for

configuring IP Addresses and troubleshooting.

Communication
Comparisons

The Table below compares key communication features between using
Advance Data Hiway, Ethernet, or DataNET.

Feature Advance

Data

Hiway

Ethernet DataNET

Speed

14.2 KB/Sec

10 M baud

2. 048 M baud

Redundant Yes

No

Yes

Number of Units in
Maxum System

248 1200

1200

2000592-001

Installation

3

Advertising