Command Descriptions,

Continued

reset

This command resets and saves the configuration parameters in non-
volatile memory.

test

This command places a selected port into a hardware diagnostic mode.
The test mode can be used to verify cable continuity and DataNET signal
levels when used in conjunction with an Oscilloscope or other test
device.

The command:

test 1

places port 1 into test mode. The device will generate poll messages on
port 1 every 50 milliseconds. The other port continues to operate
normally. The command:

test off

turns off test mode. Only one port at a time may be in test mode.

timeout

This command may be used to disable the user login timeout. Normally,
if a user has not issued a CLI command for five minutes, the device will
automatically shut down the user’s login session. This command may be
used to defeat (and re-enable) this timeout:

timeout off

Disables timeout. The device will not automatically
log out the user; regardless of the time elapsed since
the user last issued a CLI command.

timeout on

Re-enables the five-minute CLI timer.