Jumper j5 settings, More information, Ancb description – Siemens ADVANCE NETWORK COMMUNICATIONS BOARD/DATANET 2000592-001 User Manual

Page 58

Advertising
background image

ANCB Description,

Continued

Jumper J5 Settings

The ANCB jumper settings for J5 are factory set and dependent upon the
product the ANCB will be used in.

Product Type

ANCB J5 Jumper Settings

Advance Network Gateway
Ethernet (ANG-EN)

Pins 3&4 are shorted, switch in 25-
ohm position. 10Base2 connector is
not normally used (not connected)

Advance Network Gateway
DataNET (ANG-DN)

Pins 1&2 are shorted, switch in 50-
ohm position. 10Base2 connector is
used as an end point for crossover
cable.

Advance Plus Analyzer

Pins 1& 2 are shorted, switch in 50-
ohm position. 10Base2 connector is
used as an end point for crossover
cable.

Maxum Analyzers with ANCB/DN
Installed

Pins 3&4 are shorted, switch in 25-
ohm position. 10Base2 connector is
not normally used (not connected)

More Information

See ANCB LEDs Description and Operation, page 49.

48

Troubleshooting

2000592-001

Advertising