Sanyo CH0951 User Manual

Page 18

Advertising
background image

18

6. Air Purging

Air and moisture remaining in the refrigerant system have

undesirable effects as indicated below. Therefore, they must

be purged completely.

pressure in the system rises

operating current rises

cooling (or heating) efficiency drops

moisture in the air may freeze and block capillary tubing

water may lead to corrosion of parts in the refrigerant sys-

tem

Air Purging with a Vacuum Pump (for Test Run)

(1) Check that each tube (both narrow and wide tubes)

between the indoor and outdoor units have been properly

connected and all wiring for the test run has been com-

pleted. Note that both narrow and wide tube service

valves on the outdoor unit are kept closed at this stage.

(2) Using an adjustable wrench or box wrench, remove the

valve caps from the service valve on both narrow and

wide tubes.

(3) Connect a vacuum pump and a manifold valve (with pres-

sure gauges) to the service port on the wide tube service

valve. (Fig. 52)

(4) With the “Lo” knob of the manifold valve open, run the

vacuum pump. The operation time for the vacuum pump

varies with tubing length and the capacity of the pump.

The following table shows the amount of time for evacua-

tion:

Table 6

The required time in the above table is calculated based on

the assumption that the ideal (or target) vacuum condition is

around 10 mmHg abs.

NOTE

Hi

Lo

Indoor unit

Outdoor unit

Manifold valve

Pressure
gauge

Vacuum pump

Fig. 52

Required time for evacuation when capacity

of 100 liter/h vacuum pump is used

If tubing length is

If tubing length is

less than 33 ft. (10 m)

more than 33 ft. (10 m)

10 min. or more

15 min. or more

CAUTION

Be sure to use a manifold valve for

air purging. If it is not available, use

a stop valve for this purpose. The

“Hi” knob of the manifold valve

must always be kept closed.

01-385 AirCon 12/11/01 4:42 PM Page 18

Advertising