Installation site selection – Sanyo CH0951 User Manual

Page 4

Advertising
background image

4

1-6. Additional Materials Required for Installation

1.

Refrigeration (armored) tape

2.

Insulated staples or clamps for connecting wire

(See local codes)

3.

Putty

4.

Refrigeration lubricant

5.

Clamps or saddles to secure refrigerant tubing

2. Installation Site Selection

2-1. Indoor Unit

AVOID:

direct sunlight.

nearby heat sources that may affect performance of the

unit.

areas where leakage of flammable gas may be expected.

places where large amount of oil mist exist.

DO:

select an appropriate position from which every corner of

the room can be uniformly cooled. (High on a wall is best.)

select a location that will hold the weight of the unit.

select a location where tubing and drain hose have the

shortest run to the outside. (Fig. 1)

allow room for operation and maintenance as well as unre-

stricted air flow around the unit. (Fig. 2)

install the unit within the maximum elevation difference (H)

above the outdoor unit and within a total tubing length (L)

from the outdoor unit as detailed in Table 3 and Fig. 3a.

Table 3

Drain hose

Indoor unit

Outside drainage

Fig. 1

*

6" (15 cm) min.

Front View

2" (5 cm) min.

*

6" (15 cm) min.

*

KS1852 only

2" (5 cm) min.

*

6" (15 cm) min.

2" (5 cm) min.

Fig. 2

INDOOR
UNIT

Tubing length (L)

OUTDOOR
UNIT

Elevation
difference (H)

Fig. 3a

Max. Allowable Tubing

Limit of Tubing

Limit of Elevation

Required Amount of

Length at Shipment

Length (L)

Difference (H)

Additional Refrigerant

Model

(ft.)

(ft.)

(ft.)

(oz./ft.)

*

25

50

23

a) 0.16

9,000 BTU

25

65

23

b) 0.27

12,000/18,000 BTU

WARNING

To prevent abnormal heat genera-

tion and the possibility of fire, do

not place obstacles, enclosures

and grilles in front of or surround-

ing the air conditioner in a way that

may block air flow.

*

If total tubing length becomes a) 25 to 50 ft. (max.), b) 25 to 65 ft. (max.) charge additional refrigerant (R22) by a) 0.16 oz./ft., b) 0.27 oz./ft.
No additional compressor oil is necessary.

Indoor unit

Floor level

Wall

Minimum height

from floor level

5 ft. (1.5 m)

Fig. 3b

For stable operation of

the air conditioner, do

not install wall-mounted

type indoor units under

5 ft. (1.5 m) from floor

level.

CAUTION

*

KHS1852 only

01-385 AirCon 12/11/01 4:41 PM Page 4