Sanyo CH0951 User Manual

Page 5

Advertising
background image

5

2-2. Outdoor Unit

AVOID:

heat sources, exhaust fans, etc. (Fig. 4)

damp, humid or uneven locations.

DO:

choose a place as cool as possible.

choose a place that is well ventilated.

allow enough room around the unit for air intake/

exhaust and possible maintenance. (Fig. 5a)

Outdoor unit

Hot air

Heat source

Exhaust fan

NO

Fig. 4

Air intake

Min. 6" (15 cm)

Air discharge

Min. 6"
(15 cm)

Min. 12"
(30 cm)

Valve side
Min. 10"
(25 cm)

Min.

7 ft.

(2 m)

Min.

7 ft.

(2 m)

Min. 6 in.
(15 cm)
Air intake

Ground

Obstacle

Obstacle above

Air discharge

Fig. 5a

CAUTION

Install the outdoor unit above snowfall line.

Do not place objects on or sit on the out-

door unit. Also, never block the air

intake/outlet or exhaust. Distortion of the

outdoor unit or incomplete combustion

may result.

Do not introduce foreign matter into the air

intake/outlet or exhaust. Do not poke them

with such objects as a stick.

provide a solid base (level concrete pad, concrete

block, 2 to 2-1/2 (CH09, 12) / 2-1/2 to 3 (CH18) in.

×

16 in. (5 to 6.5 / 6.5 to 7.5

×

40 cm) beams or equal),

a minimum of 4 in. (10 cm) above ground level to

reduce humidity and protect the unit against possible

water damage and decreased service life (Figs. 5b

and 5c).

use lug bolts or equal to bolt down unit, reducing

vibration and noise.

Air intake

Concrete
or equal

Min. 4"
(10 cm)

Anchor bolts
(4 pcs)

About 16" (40 cm)

CH09, 12: 2 to 2-1/2" (5 to 6.5 cm)
CH18: 2-1/2 to 3" (6.5 to 7.5 cm)

CAUTION

A solid base must not cover

the hole of the bottom plate.

Drain holes

Fig. 5c

Fig. 5b

01-385 AirCon 12/11/01 4:41 PM Page 5